Contactor and Relay Terminal Markings

Identify common IEC contactor coil, power, auxiliary-contact, and overload terminal markings, with device-specific limits and contact examples.

Last updated:

Terminal lookup

The following are common IEC-style markings found on ABB contactors, auxiliary contacts, and overload relays. They identify terminal functions within the applicable product family. They are not a universal numbering system for every relay or controller.

Common IEC contactor and relay terminal functions
MarkingTypical functionImportant distinction
A1, A2Operating coil terminalsRead the coil voltage/frequency and polarity markings where applicable. The coil rating is separate from the main power circuit.
1/L1, 3/L2, 5/L3Main circuit line-side terminalsFollow the exact product diagram and any direction-of-feed restrictions.
2/T1, 4/T2, 6/T3Corresponding main circuit load-side terminalsTerminal numbers do not establish phase sequence or connected motor rotation.
13–14Normally open auxiliary contactA low-current control contact, not another main power pole. Verify its utilization rating.
21–22Normally closed auxiliary contactContact state is referenced to the device’s defined normal condition.
33–34 / 43–44Additional normally open auxiliary contacts on applicable blocksUse the block schematic to establish which pairs exist.
11–12–14A common changeover contact pattern: common, NC, NOApplies only where the device diagram uses this numbering; not the same arrangement as a 13–14 NO pair.
95–96Common overload relay trip contact, normally closed before tripOverload state and reset status determine operation; verify the relay instructions.
97–98Common overload relay trip indication contact, normally open before tripDo not assume every overload relay provides this pair.
PE / protective-earth symbolProtective bonding terminal where markedNot a coil return or a general-purpose signal reference.

Read the contact state

For an ordinary non-latching contactor, the drawing generally shows contacts with the coil de-energized. A normally open auxiliary closes when the contactor operates; a normally closed auxiliary opens. A trip contact instead relates to the relay’s defined untripped/tripped condition.

A latching relay, maintained actuator, or special function block needs its own definition of normal state. Contact numbers and a NO/NC label do not establish safety integrity, positive opening, or suitability for a safety circuit.

As a reading example, a coil marked A1/A2 and an auxiliary pair marked 13/14 represent different functions. Do not connect power to a terminal pair merely because its number appears in this chart.

Check the actual assembly

  1. Record the complete device catalog number, coil code, and installed auxiliary or overload blocks.
  2. Locate the terminal diagram supplied with those exact parts. Add-on blocks can change which numbers are available.
  3. Check control voltage, AC/DC requirements, polarity where marked, contact ratings, conductor range, and connection instructions.
  4. Compare the diagram with the project control drawing. Record discrepancies before replacement or testing.

Use the schematic symbol legend to distinguish the drawn contact and coil. Keep observed markings and test conditions in an electrical test record.