CT and PT Polarity and Terminal Markings

Read current- and voltage-transformer polarity conventions, distinguish H/X and P/S labels, and identify manufacturer diagrams and secondary-circuit limits.

Last updated:

Polarity and winding marks

Polarity marks identify a relationship used when interpreting transformer connections and instrument signals. They do not identify a safe-to-touch point or a complete meter wiring arrangement. Current transformers and voltage transformers have different secondary-circuit handling requirements.

Selected instrument-transformer conventions
Marking contextWhat it identifiesWhat must be verified
H1 / H2 on a CTThe documented primary polarity/orientation referenceA window CT may mark a side of the opening rather than expose primary terminals.
X1 / X2 on a CTThe documented secondary terminal/polarity pairThe relationship to H1, the meter current input, and the exact wiring diagram.
P1 / P2 and S1 / S2Another primary/secondary marking conventionUse the actual manufacturer diagram; do not relabel an unknown device from appearance.
Dot / polarity markCorresponding instantaneous polarity references in the stated conventionNot a statement of RMS voltage, ratio, or permitted grounding point.
PT / VTA potential/voltage transformer applicationThe nameplate, voltage ratio, fusing, secondary rating, and instrument wiring.
Ratio / burden / accuracy informationSeparate ratings relevant to the measurement applicationA correct ratio alone does not prove an adequate or correctly connected measurement system.

CT reference path

Illustrative CT orientation and closed secondary burden path. H1 is the example primary reference side; X1 and X2 identify the example secondary pair.H1 reference sidePrimary pathX1X2BurdenPolarity illustration only — not an instrument connection procedure.
The closed path is illustrative. Terminal orientation, secondary grounding, shorting facilities, burden and wiring come from the exact equipment diagrams.

The Schneider FAQ identifies the polarity-marked CT side in its stated application. A meter also needs the current channel associated with the correct voltage phase and a correctly interpreted direction. A polarity or phase-association error cannot be diagnosed only by a CT ratio calculation.

Never open a CT secondary while its primary is energized. Use the manufacturer’s documented shorting and isolation arrangements through the qualified work procedure; this drawing does not supply that procedure.

Voltage transformer convention

A voltage transformer’s primary and secondary polarity references describe corresponding winding relationships. They are not a direction to connect its secondary like a CT burden circuit. In particular, a voltage-transformer secondary must not be shorted as though it were a CT secondary.

Confirm ratio, rated voltage, polarity, fusing/protection, grounding arrangement, burden, and meter-channel connections from the manufacturer and project diagrams. Different instrument-transformer product families can use different terminal conventions.

Collect the exact diagrams

  1. Record the instrument-transformer catalog, ratio, polarity marks, orientation, and terminal identifiers.
  2. Obtain the transformer and instrument connection drawings for the actual configuration.
  3. Check phase association, secondary ratings/burden, protective and isolation arrangements, and applicable grounding requirements.
  4. Have unresolved markings or discrepancies reviewed before connection or testing.

The existing CT ratio and meter multiplier calculators perform separate numerical tasks. Record actual test evidence in the test record.

Sources

Browse all reference tables, guides, and templates