Breaker Sizing Calculator

Determine the minimum circuit breaker trip rating based on load current, continuous duty factor (NEC 210.20A), and standard breaker sizes per NEC 240.6.

Load Parameters

Calculates automatically as you type

Enter load current to select breaker size

Circuit Breaker Sizing per NEC Article 240

The circuit breaker is the last line of defense between a wiring fault and a building fire. A breaker sized too large allows conductors to overheat before tripping; a breaker sized too small causes nuisance tripping that disrupts operations and frustrates occupants. NEC Article 240 governs overcurrent protection sizing, establishing a precise relationship between breaker ratings, conductor ampacity, and load characteristics. The fundamental rule is simple: the breaker rating must not exceed the ampacity of the conductors it protects (NEC 240.4), with carefully defined exceptions for motor circuits, transformer secondaries, and tap conductors.

Standard breaker sizes follow NEC 240.6(A): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, and 6000 amperes. The 'next standard size up' rule (NEC 240.4(B)) permits using the next higher standard rating when the calculated load falls between standard sizes — but only for non-motor loads and only for conductors rated 800A or less. For example, a 38A non-continuous load on 8 AWG copper (50A at 75°C) requires a 40A breaker — not a 35A.

Continuous loads — defined as loads expected to operate for 3 hours or more — require special treatment. The overcurrent device must be rated at not less than 125% of the continuous load plus 100% of the non-continuous load (NEC 210.20(A)). A commercial lighting panel with 80A continuous lighting load requires a breaker rated at least 80 × 1.25 = 100A. This 125% factor ensures the breaker's internal bimetallic strip or electronic trip mechanism does not overheat during sustained operation. Some 100%-rated breakers (Square D HG, Eaton FD 100%) are specifically listed for continuous loading at their full rated current, eliminating the 125% requirement.

Residential panel sizing involves a formulaic approach. A typical US dwelling unit serves a 200A main panel containing: 20A (kitchen, bathroom, laundry, garage GFCI/AFCI circuits), 15A (general lighting), 30A (electric dryer), 40-50A (electric range), and 30-60A (air conditioning or heat pump). NEC 220.82 provides the optional calculation for dwelling units: 100% of the first 10 kVA plus 40% of the remainder, which often results in a significantly lower service size than the standard calculation. A 2,500 sq ft home with electric range, dryer, A/C, and water heater might calculate to only 125A using the optional method — comfortably served by a 150A or 200A service.

Commercial and industrial facilities require a different breaker sizing philosophy. Main breakers must be rated for the available fault current at the service entrance (SCCR — Short-Circuit Current Rating), which can range from 10,000A at a residential panel to 200,000A at an industrial switchboard. Breakers with insufficient interrupting capacity will fail catastrophically during a fault — violating NEC 110.9 and creating an extreme arc-flash hazard. Series-rated systems use a tested combination of a larger upstream breaker and a smaller downstream breaker to achieve adequate fault rating at reduced cost.

Tap conductor protection is governed by NEC 240.21, which provides several exceptions to the general rule that breakers must be at the supply end of conductors. The 10-foot tap rule (240.21(B)(1)) permits unprotected conductors up to 10 feet if the ampacity is at least 10% of the upstream breaker rating, the conductors are enclosed in a raceway, and they terminate in a single overcurrent device. The 25-foot tap rule (240.21(B)(2)) requires ampacity of at least one-third of the upstream device rating. These rules are critical for designing Panel-to-sub-panel feeder taps, transformer secondary connections, and generator paralleling switchgear.

Frequently Asked Questions

How do I determine breaker size for a branch circuit?

Start with the load current. For non-continuous loads, select the next standard breaker size equal to or greater than the load — but never exceeding the conductor ampacity. For continuous loads, multiply by 1.25 and select a breaker at or above that value. A 40A continuous load: 40 × 1.25 = 50A breaker minimum. Then verify the conductor ampacity supports the breaker rating: 6 AWG copper (65A at 75°C) is adequate. For mixed continuous/non-continuous loads, the breaker rating ≥ (1.25 × continuous) + (1.0 × non-continuous).

What is the next standard size up rule?

NEC 240.4(B) permits rounding up to the next standard breaker size (per NEC 240.6(A)) when the calculated load falls between sizes — but only for branch circuits serving non-motor loads where conductors are not part of a multi-outlet branch circuit over the values specified in 210.3, and only when the conductor ampacity matches a non-standard value. This applies to conductors with ampacity up to 800A. Above 800A, the breaker must be sized at or below the conductor ampacity — no rounding up.

Do I need GFCI or AFCI protection?

NEC 2023 significantly expanded both requirements. GFCI (210.8): required for kitchen countertop receptacles, bathrooms, garages, outdoor, crawl spaces, unfinished basements, laundry areas, sinks with receptacles within 6 feet, and boathouses. AFCI (210.12): required in dwelling unit bedrooms, living rooms, family rooms, dining rooms, kitchens, hallways, closets, and similar rooms. Dual-function AFCI/GFCI breakers satisfy both requirements and are increasingly the default choice for dwelling unit circuits.

What is the difference between standard and 100%-rated breakers?

Standard breakers must be derated to 80% for continuous loads — a 100A standard breaker can only serve 80A of continuous load. 100%-rated breakers (specifically listed and marked) can carry their full rating continuously: a 100A 100%-rated breaker serves 100A continuously. 100%-rated breakers require larger enclosures for heat dissipation and are significantly more expensive. They're used when the 125% continuous load factor would otherwise require an unnecessarily large panel and conductors.

How do I handle series-rated breaker systems?

Series-rated systems use a tested combination of an upstream (main) breaker with high interrupting rating to protect a downstream breaker with lower interrupting rating. For example: a 65kAIC main breaker protects a 22kAIC branch breaker in a panel where the available fault current is 40kA. The combination must be specifically tested and listed per UL 489 — you cannot arbitrarily combine breakers. NEC 240.86 governs series-rated systems, and the panel must be marked with the series rating.

How do I select a main breaker for a dwelling unit panel?

Use NEC 220.82 (optional calculation): total connected load = general lighting (3 VA/sq ft × floor area) + all fixed appliances + HVAC load. Apply: 100% of first 10 kVA + 40% of remainder. For a 2,000 sq ft home: lighting = 6,000 VA, appliances = 15,000 VA, HVAC = 5,000 VA → total = 26,000 VA. First 10 kVA at 100% = 10,000, remainder at 40% = 6,400, total = 16,400 VA ÷ 240V = 68A → 100A service/panel is adequate. Most new construction installs 200A for future expansion.

What is short-circuit current rating (SCCR) and why does it matter?

SCCR is the maximum fault current that equipment can safely withstand or interrupt. NEC 110.9 requires overcurrent devices (breakers) to have an interrupting rating sufficient for the available fault current. NEC 110.10 requires all components (panels, disconnects, motor starters) to have adequate withstand ratings. A typical utility transformer provides 10,000-25,000A fault current at a residential panel and 22,000-65,000A at commercial switchgear. Installing a 10,000A breaker where 40,000A fault current is available is a lethal code violation.

Related Calculators

Authoritative Standards

  • NEC Article 240 — Overcurrent Protection
  • NEC 240.4 — Protection of Conductors
  • NEC 240.6(A) — Standard Ampere Ratings
  • NEC 240.21(B) — Feeder Tap Conductor Rules
  • NEC 210.20(A) — Continuous and Non-Continuous Load Protection
  • NEC 110.9 — Interrupting Rating

Project Explorer

No Projects Found