Single-Phase & Three-Phase Voltage Drop Calculator
- Code basis
- NEC 2023, 210.19 / 215.2
- Editions
- 2017, 2020, 2023
- Modes
- Single-phase, three-phase
- Conductor sizes
- 24
- Materials
- Copper, aluminum
- Methods
- Table 8 DC resistance
- Targets
- 3% branch, 5% combined
Circuit
Voltage options change with the mode. A two-pole 208 V circuit from a three-phase panel is a single-phase load.
Conductor
Uses launch-safe Table 8 resistance data. Table 9 impedance is held back until verification closes.
Voltage drop
Over target3.89%
8 AWG copper, 150 ft one-way at 40 A. Target is 3 percent.
- Volts dropped
- 9.34 V
- Voltage at load
- 230.7 Vfrom 240 V nominal
- Smallest size within target
- 6 AWGDrop only. Check ampacity separately.
- Resistance used
- 0.778 ohm/kft
- Drop is 3.9 percent, above the 3 percent target. 6 AWG is the smallest tabulated size that meets it over 150 ft.
- The 3 and 5 percent figures are recommendations in informational notes, not enforceable requirements. Some jurisdictions and some other standards do enforce a limit.
- Drop is calculated from direct-current resistance at 75 degrees C. The unverified Table 9 impedance path is not shipped in the public calculator.
Derivation
| Step | Basis | Effect | Value |
|---|---|---|---|
| DC resistance, 8 AWG copper stranded at 75 C | Chapter 9, Table 8 | — | 0.778 ohm/kft |
| Circuit resistance over 150 ft, doubled for the return conductor | — | × 2 | 0.2334 ohm |
| Drop at 40 A | — | — | 9.34 V |
| Share of the 240 V nominal system voltage | 210.19(A), Informational Note | — | 3.89 % |
Drop by size
| Size | Ohm/kft | Drop | Percent | Verdict |
|---|---|---|---|---|
| 12 AWG | 1.98 | 23.76 | 9.90% | Over target |
| 10 AWG | 1.24 | 14.88 | 6.20% | Over target |
| 8 AWG | 0.778 | 9.34 | 3.89% | Over target |
| 6 AWG | 0.491 | 5.89 | 2.46% | Within target |
| 4 AWG | 0.308 | 3.70 | 1.54% | Within target |
| 3 AWG | 0.245 | 2.94 | 1.23% | Within target |
| 2 AWG | 0.194 | 2.33 | 0.97% | Within target |
Every row assumes 40 A over 150 ft at 240 V, single-phase. Ampacity is not checked here.
Calculated against the NEC 2023 edition using 210.19(A) informational note, 215.2(A) informational note, Chapter 9, Table 8. Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.
Not covered by this tool
- Table 9 impedance mode is not publicly selectable until the data verification gate closes.
- Conductor operating temperature other than 75 degrees C. Resistance falls as a conductor runs cooler, so a lightly loaded circuit drops slightly less than shown.
- Coated copper and solid conductors, both of which are tabulated separately and run a few percent higher.
- Harmonic current on the neutral of a three-phase, four-wire system supplying nonlinear load.
- Motor starting inrush, where momentary drop is judged against the equipment manufacturer's tolerance rather than these percentages.
- Ampacity, overcurrent protection and raceway fill, which are covered by the other calculators.
Data last verified
Calculation Method
Four steps, matching a hand calculation from the conductor properties table.
Step 1
Resistance lookup
Reads ohms per 1000 ft from the stranded uncoated resistance data at 75 degrees C. Table 9 impedance mode stays hidden until the R/X dataset is verified for launch.
Step 2
Circuit length
Single-phase doubles the one-way length, because current returns on a second conductor. Three-phase multiplies by the square root of three, which accounts for the 120-degree displacement between line currents.
Step 3
Drop at the operating current
Multiplied by the current actually flowing. Use the running load, not the breaker rating: a 50 A breaker on a 32 A load produces a 32 A drop.
Step 4
Percentage of nominal
Volts dropped divided by nominal system voltage, compared against the selected target. Exceeding the target is reported as a caution, never as a failure.
Drop is calculated at the operating current, not at the design current used for conductor sizing. The 125 percent continuous-load multiplier is a sizing rule for conductors and overcurrent devices; it is not a statement about how much current flows.
Recommended Limits and Their Actual Status
The single most misrepresented point in this calculation. Only the last row is enforceable.
| Segment | Recommended max | Status | Basis |
|---|---|---|---|
| Branch circuit, panelboard to outlet | 3% | Recommendation | 210.19(A), Informational Note |
| Feeder, service equipment to panelboard | 3% | Recommendation | 215.2(A), Informational Note |
| Feeder and branch circuit combined | 5% | Recommendation | Both notes read together |
| Sensitive equipment with a stated tolerance | Per nameplate | Manufacturer requirement | Equipment listing and instructions |
The two percentages are not additive in the direction most people assume. A feeder held to 3 percent leaves 2 percent for every branch circuit behind it, not 3 more. Where a long feeder is unavoidable, holding it to 1 percent buys back headroom downstream.
Maximum One-Way Run at 3 Percent
Copper at 240 V single-phase. Use it as a sanity check before opening the calculator.
| Size | 20 A | 40 A | 60 A | 100 A |
|---|---|---|---|---|
| 14 AWG | — | — | — | — |
| 12 AWG | 90 ft | — | — | — |
| 10 AWG | 145 ft | — | — | — |
| 8 AWG | 230 ft | 115 ft | — | — |
| 6 AWG | 365 ft | 180 ft | 120 ft | — |
| 4 AWG | 580 ft | 290 ft | 190 ft | — |
| 2 AWG | 925 ft | 460 ft | 305 ft | 185 ft |
| 1/0 AWG | 1475 ft | 735 ft | 490 ft | 295 ft |
| 2/0 AWG | 1860 ft | 930 ft | 620 ft | 370 ft |
| 4/0 AWG | 2960 ft | 1480 ft | 985 ft | 590 ft |
Halve these lengths for a 120 V circuit at the same current: drop percentage is inversely proportional to system voltage. Aluminum of the same size reaches roughly 60 percent of the distance.
When Drop Governs the Size
Drop rarely decides a short circuit and frequently decides a long one. These are the cases that come up.
| Installation | Typical outcome | Action |
|---|---|---|
| 20 A receptacle circuit to a detached garage, 180 ft | Ampacity allows 12 AWG; drop needs 8 AWG | Upsize the ungrounded conductors and increase the grounding conductor proportionally. |
| 100 A subpanel feeder, 240 V, 200 ft | Drop lands between 3 and 5 percent | Acceptable as a feeder alone. Budget the remainder for the branch circuits downstream. |
| 480 V three-phase feeder, 400 ft | Usually passes at the ampacity-driven size | Higher voltage carries the same power at lower current, so drop is rarely the constraint. |
| Well pump on 240 V, 350 ft of 10 AWG | Well over 3 percent under running load | Upsize the conductors. Starting current makes the momentary drop several times larger. |
| EVSE at 48 A on a 240 V circuit, 120 ft | Marginal on 6 AWG copper | Check 4 AWG. Charging is a continuous load, so the drop is sustained rather than intermittent. |
| 120 V lighting branch at 12 A, 90 ft | Passes on 12 AWG | No change needed. At 120 V a short run still leaves headroom for the feeder ahead of it. |
Choosing How to Fix an Excessive Drop
Six options, ordered from the most common to the most situational. Upsizing is not always the cheapest.
Increase the conductor size
The direct fix and usually the cheapest. Resistance roughly halves for every three AWG sizes, so two sizes up cuts drop by about a third. Confirm the terminations and raceway accept the larger conductor before pricing it.
Run parallel sets
Two sets halve the resistance. Permitted from 1/0 upward, and every set must match in size, material, insulation, length and termination method. Practical where a single conductor would exceed what the equipment lugs accept.
Raise the system voltage
The same power at 480 V draws less than half the current it does at 208 V, and drop scales with current. Where a 277/480 V system is available, feeding at the higher voltage and transforming locally often costs less than upsizing copper.
Move the distribution point
Drop scales linearly with length. A subpanel located near the load turns one long run at full load current into a short run plus several short branch circuits, which is frequently the lowest-cost answer on a long site.
Reallocate the budget between segments
The 5 percent figure covers the feeder and the branch circuit together. A feeder held to 1 percent leaves 4 percent for the branch circuits behind it, which can be the difference between upsizing a 300 ft feeder and upsizing nothing.
Switch material deliberately, not by default
Aluminum of the same size has roughly 1.6 times the resistance of copper, so matching a copper run generally takes two sizes larger. On a long feeder that is still often cheaper per foot. Confirm the terminations are listed for aluminum.