Conduit Fill Calculator for Multiple Wire Sizes
- Code basis
- NEC 2023, Ch. 9
- Tables used
- 1, 4, 5, 5A
- Raceway types
- 8
- Insulation types
- 6
- Conductor sizes
- 14 AWG – 1000 kcmil
- Stranding
- Concentric, compact
- Fill limits
- 53 / 31 / 40 / 60%
Raceway
Available trade sizes vary by type; the size list updates accordingly.
Conductors
One group per size and insulation type. Any combination is supported.
Group 1
Group 2
Fill
Pass26.8%
40 percent permitted for 9 conductors in 3/4 in EMT.
- Conductor area
- 0.1431 in²of 0.213 in² permitted
- Area to spare
- 0.0699 in²
- Smallest that fits
- 3/4 in26.8% fill
- 6 × 12 AWG THHN/THWN-2
- 3 × 10 AWG THHN/THWN-2
Area by group
| Group | Each | Total | Share |
|---|---|---|---|
| 6 x 12 AWG THHN/THWN-2 | 0.0133 | 0.0798 | 55.8% |
| 3 x 10 AWG THHN/THWN-2 | 0.0211 | 0.0633 | 44.2% |
Raceway internal area is 0.533 in2, of which 0.213 in2 may be occupied.
Calculated against the NEC 2023 edition using Chapter 9, Table 1, Chapter 9, Table 4, Chapter 9, Table 5, Chapter 9, Table 5A. Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.
Not covered by this tool
- Compact stranded conductors in THW, THHW and the RHH/RHW/USE group, which this tool does not offer as insulation types.
- Cable assemblies such as UF, NM and MC, which are treated as a single conductor using the manufacturer's actual dimensions.
- Conduit bodies, boxes and wireways, which are sized by different rules.
- Bending radius, pulling tension and lubrication, none of which the fill limit addresses.
Data last verified
Calculation Method
Four steps, equivalent to a manual Chapter 9 calculation.
Step 1
Conductor area
Cross-sectional area per conductor from Table 5, or Table 5A where the group is compact stranded, multiplied by quantity and summed across all groups.
Step 2
Raceway area
Internal cross-sectional area for the selected type and trade size from Table 4.
Step 3
Permitted fill
Determined by conductor count per Table 1. The permitted area is read from the published column rather than recomputed, so marginal results agree with the printed table.
Step 4
Comparison
Total conductor area against permitted area, reported as a percentage of the full internal area with remaining headroom in square inches.
All conductors count toward fill, including the neutral and the equipment grounding conductor. The derating count under Article 310 is different: it includes current-carrying conductors only.
Permitted Fill by Conductor Count
Fill limits are set by conductor quantity, not by raceway type or material.
| In the raceway | Permitted fill | Basis |
|---|---|---|
| 1 conductor | 53% | The full remaining bore is available for the pull. |
| 2 conductors | 31% | Most restrictive case. Two round conductors pack inefficiently and leave minimal pulling clearance. |
| 3 or more | 40% | Applies to the majority of installations. |
| Nipple, 24 in or less | 60% | A short length between enclosures presents negligible pulling length. |
Conductor Areas
Approximate area in square inches per insulated conductor, for verifying a result by hand.
| Size | THHN / THWN-2 | XHHW / XHHW-2 | TW / THW |
|---|---|---|---|
| 14 AWG | 0.0097 | 0.0139 | 0.0139 |
| 12 AWG | 0.0133 | 0.0181 | 0.0181 |
| 10 AWG | 0.0211 | 0.0243 | 0.0243 |
| 8 AWG | 0.0366 | 0.0437 | 0.0437 |
| 6 AWG | 0.0507 | 0.059 | 0.0726 |
| 4 AWG | 0.0824 | 0.0814 | 0.0973 |
| 2 AWG | 0.1158 | 0.1146 | 0.1333 |
| 1/0 AWG | 0.1855 | 0.1825 | 0.2223 |
| 2/0 AWG | 0.2223 | 0.219 | 0.2624 |
| 4/0 AWG | 0.3237 | 0.3197 | 0.3718 |
| 250 kcmil | 0.397 | 0.3904 | 0.4596 |
| 350 kcmil | 0.5242 | 0.5166 | 0.5958 |
| 500 kcmil | 0.7073 | 0.6984 | 0.7901 |
EMT Capacity by Trade Size
Internal dimensions and the area permitted for three or more conductors. Other raceway types are available in the calculator.
| Trade size | Internal dia. | Total area | 40% area |
|---|---|---|---|
| 1/2 in | 0.622 | 0.304 | 0.122 |
| 3/4 in | 0.824 | 0.533 | 0.213 |
| 1 in | 1.049 | 0.864 | 0.346 |
| 1-1/4 in | 1.38 | 1.496 | 0.598 |
| 1-1/2 in | 1.61 | 2.036 | 0.814 |
| 2 in | 2.067 | 3.356 | 1.342 |
| 2-1/2 in | 2.731 | 5.858 | 2.343 |
| 3 in | 3.356 | 8.846 | 3.538 |
| 3-1/2 in | 3.834 | 11.545 | 4.618 |
| 4 in | 4.334 | 14.753 | 5.901 |
Common Errors
Four errors responsible for most fill-related inspection failures.
Omitting the equipment grounding conductor
All conductors count toward fill, including the equipment grounding conductor and the neutral. The derating count excludes the EGC, so a count carried over from a derating calculation is one conductor short.
Treating 31 percent as the lenient limit
The two-conductor limit is the most restrictive of the three. Adding a third conductor raises the permitted area from 31 to 40 percent, so a failing two-wire pull can pass once the grounding conductor is included.
Itemising a cable as separate conductors
A multiconductor cable counts as one conductor, using the major diameter of its cross-section. A bundle of single conductors without an overall covering is not a cable and is calculated individually. UF, NM and MC are excluded here because they require manufacturer dimensions.
Equating compliant fill with a practical pull
Fill compliance is necessary but not sufficient. A raceway at 39 percent with four 90-degree bends and no lubricant may be impractical to pull. Verify jam ratio, bend count and pulling tension separately, and note that derating may require larger conductors regardless.