Load Schedule Calculator

Build a complete load schedule with multiple entries, demand factors, and continuous load analysis. Determines minimum service amperage per NEC 220.

System

Load Schedule

Continuous
Continuous
Continuous
Continuous

Add loads to calculate service sizing

Electrical Load Schedule per NEC Article 220

A load schedule is the master ledger of an electrical system — every circuit, every load, every ampere accounted for. It is the foundation from which all other electrical design flows: conductor sizing, breaker selection, transformer kVA, generator sizing, and service entrance calculations. A poorly prepared load schedule cascades into undersized equipment, tripped breakers, overloaded transformers, and code violations. NEC Article 220 provides the methods for calculating branch circuit, feeder, and service loads, including mandatory demand factor application.

NEC 220 provides two methods for residential load calculation: the Standard Method (Parts I-IV) and the Optional Method (Part V, Section 220.82). The Standard Method requires itemizing all loads by category — general lighting (Table 220.12 at 3 VA/ft²), small appliance circuits (2 × 1,500 VA per 220.52(A)), laundry circuit (1,500 VA per 220.52(B)), fixed appliances (nameplate rating), motors (125% of largest motor FLC per 430.24), HVAC (larger of heating or cooling per 220.60), and applying specific demand factors for each category. The Optional Method provides a simplified calculation for dwelling units: first 10 kVA at 100%, remainder at 40% — but requires the dwelling to have electric cooking or space heating.

Commercial load calculations follow NEC 220.12 for general lighting (VA per square foot by occupancy type), NEC 220.14 for receptacles, and NEC 220.44 for receptacle demand factors. A critical difference from residential: commercial receptacle loads get their own demand factor calculation — first 10 kVA at 100%, remainder at 50% (NEC 220.44). Motor loads must use the largest motor at 125% plus all others at 100% (NEC 430.24). The continuous load multiplier of 125% per NEC 215.2(A)(1) applies to any load expected to operate for 3+ hours.

NEC demand factors recognize that not all loads operate simultaneously. Key demand factor tables: NEC Table 220.42 for general lighting (first 3,000 VA at 100%, next 3,001-120,000 VA at 35%, remainder at 25% for dwellings). NEC Table 220.54 for electric dryers (first 4 at 100%, 5th at 80%, 6th at 70%... down to 25% for 23+ units). NEC Table 220.55 for cooking equipment (column B and column C provide demand factors by number of appliances — 12 ranges at 8 kW demand each instead of 12 × 12 kW = 144 kW). NEC Table 220.56 for kitchen equipment in commercial facilities.

Panel scheduling — the physical layout of circuits within a panelboard — is an engineering discipline beyond simply assigning breaker slots. Phase balance requires distributing single-phase loads evenly across the three phases (A-B-C) so that neutral current is minimized. Maximum imbalance is typically limited to 10-15% between phases. Circuit grouping should co-locate related loads (e.g., all kitchen circuits on adjacent breakers) for operational clarity. Spare capacity planning: ANSI/NECA 1 recommends 20-25% spare breaker positions and 15-20% spare capacity in feeders for future additions. Over-filling a panel leaves no room for tenant improvements or technology upgrades.

Load schedule documentation should include: circuit number, breaker size (A), wire size, conduit/raceway reference, connected load (VA and A), demand load (VA), phase assignment (A/B/C), and load description. The schedule calculates total connected load, total demanded load, and phase balance. For multi-panel facilities, a feeder schedule rolls up panel totals to distribution boards, and distribution board totals roll up to the main switchgear and service entrance. Each level applies its own demand factors per NEC 220. This hierarchical approach prevents double-dipping demand factors — a mistake that undersizes upstream equipment.

Frequently Asked Questions

What is a demand factor?

A demand factor is the ratio of maximum demand to total connected load, expressed as a percentage. Not all loads operate simultaneously — a demand factor of 50% means peak usage is only half of the total connected capacity. NEC provides mandatory demand factors for specific load types: lighting (Table 220.42), cooking equipment (Table 220.55), dryers (Table 220.54), kitchen equipment (Table 220.56). Applying demand factors reduces the calculated load below the sum of all connected devices, which directly reduces transformer and service entrance sizes — often saving thousands in equipment costs.

What is the 125% continuous load factor?

Per NEC 210.19(A)(1), 215.2(A)(1), and 230.42(A)(1): conductors and overcurrent devices must be sized at 125% of the continuous load (loads expected to operate for 3+ hours). A 20A continuous load requires a 25A-rated conductor and a 25A or larger breaker. This factor applies ON TOP of demand factor calculations — first apply demand factors to get total demanded load, then apply 125% to the continuous portion. Non-continuous loads are added at 100%. Total sizing = (continuous × 1.25) + (non-continuous × 1.00).

How do I handle mixed loads?

Group loads by NEC category: (1) General lighting per Table 220.12 VA/ft², (2) small appliance circuits at 1,500 VA each per 220.52, (3) fixed appliances at nameplate rating, (4) motor loads per Article 430 (largest at 125%, others at 100%), (5) HVAC per 220.60 — use larger of heating OR cooling, not both. Apply specific demand factors per category. Sum all demanded loads at each panel. For multi-panel systems, repeat at each hierarchy level. The total demanded load at each point determines feeder/transformer size.

What is the difference between connected load and demand load?

Connected load is the arithmetic sum of all nameplate ratings (e.g., 150 kVA total). Demand load is the calculated peak that will actually occur simultaneously after applying demand factors (e.g., 95 kVA after factors). Real-world peak demand typically falls between 50-80% of connected load for commercial buildings and 30-50% for multi-family residential. Service entrance, feeders, and transformers are sized for demand load — using connected load would result in dramatically oversized (and expensive) equipment.

How much spare capacity should I plan?

Industry best practice: 20-25% spare breaker positions in panelboards (ANSI/NECA 1 recommendation), 15-20% spare capacity in feeders and transformers, 25-40% spare conduit fill for future conductor additions. For speculative commercial spaces (shell buildings, tenant fit-up): size service and distribution for 125% of initial tenants plus 10-20% future. Data centers: plan for 3-5 years of IT load growth at 15-25% annually. The cost of oversizing during initial construction is far less than retrofitting — service entrance upgrades typically cost 5-10× the original premium for additional capacity.

How do I balance a three-phase panel?

List all single-phase loads and their VA ratings. Assign to phases A, B, C such that total VA per phase is within 10-15% of average. Three-phase loads automatically distribute evenly. Tool: create three running totals; assign each new circuit to the lowest-total phase. For panels with many single-phase circuits, use a spreadsheet to iterate. Phase imbalance increases neutral current — excessive imbalance can overload the neutral conductor. For wye-connected systems with triplen harmonics, neutral current exists even with perfect phase balance.

How does load schedule relate to arc flash labeling?

The load schedule feeds the short-circuit study (determining available fault current at each panel), which feeds the arc flash study (determining incident energy at each panel). Changes to the load schedule — adding motors, upgrading the service, paralleling transformers — can change available fault current and therefore arc flash hazard levels. NEC 110.16 requires arc flash labels on equipment, and those labels must be updated when modifications affect the hazard. A properly maintained load schedule is the starting point for keeping arc flash studies current.

Related Calculators

Authoritative Standards

  • NEC Article 220 — Branch-Circuit, Feeder, and Service Load Calculations
  • NEC Table 220.12 — General Lighting Loads by Occupancy
  • NEC Table 220.42 — Lighting Load Demand Factors
  • NEC Table 220.55 — Cooking Equipment Demand Factors
  • NEC Table 220.56 — Kitchen Equipment Demand Factors
  • ANSI/NECA 1 — Standard for Good Workmanship in Electrical Construction

Project Explorer

No Projects Found