Electrical Unit Converter

Convert between all common electrical units — voltage, current, resistance, power, energy, frequency, capacitance, and inductance. Includes HP, BTU, RPM, and other practical engineering units.

Input

Converts to all units in real time

Enter a value to convert

Electrical Unit Conversion Reference

Electrical engineering spans a staggering range of units — from picofarads (10⁻¹² F) in circuit board design to megavolt-amperes (10⁶ VA) in power system planning. Accurate unit conversion is critical because errors compound through design calculations: confusing kW with kVA undersizes transformers by 10-20%, misinterpreting motor HP types can oversize equipment by 30%, and mixing up temperature scales invalidates every ampacity derating calculation. This reference covers the most common (and most error-prone) electrical unit conversions.

Power unit conversions are the most frequent source of professional embarrassment. Real power: 1 kW = 1,000 W = 1.341 HP (mechanical) = 3,412 BTU/hr. Apparent power: 1 kVA = 1 kW only at unity power factor (PF = 1.0). At PF 0.85: 100 kVA delivers only 85 kW of useful work — the remaining 15 kVAR is reactive power that does no work but must be carried by conductors and transformers. Reactive power: 1 kVAR flows between source and load without doing work but requires full conductor capacity. The power triangle: kVA² = kW² + kVAR², PF = kW/kVA, and the angle θ = arccos(PF).

Energy conversions bridge electrical and thermal domains: 1 kWh = 3,600 kJ = 3,412 BTU = 860 kcal. Energy cost calculations require consistent units: electricity is billed in kWh, gas in therms (1 therm = 100,000 BTU = 29.3 kWh), and thermal systems use BTU/hr for heating capacity. A common industrial comparison: an electric heater at $0.10/kWh costs $29.30/therm-equivalent vs natural gas at $1.00/therm — electric heating costs 29× more in raw energy. However, electric heating is 100% efficient at point of use vs 80-95% for gas furnaces.

Temperature conversions are essential for conductor sizing and derating: °C = (°F - 32) × 5/9 and °F = °C × 9/5 + 32. Critical reference temperatures in electrical engineering: NEC ampacity tables assume 30°C (86°F) ambient, IEC tables assume 40°C (104°F) ambient — this 10°C difference is why NEC and IEC ampacity values differ for the same conductor. Conductor resistance calculations use 75°C (167°F) reference temperature. Insulation temperature ratings: 60°C, 75°C, 90°C per NEC Table 310.16; insulation fails catastrophically when exceeded.

SI prefixes span 24 orders of magnitude in electrical engineering. Common prefixes: pico (p, 10⁻¹²) — capacitance in RF circuits; nano (n, 10⁻⁹) — capacitance, time constants; micro (μ, 10⁻⁶) — capacitance, current in sensors; milli (m, 10⁻³) — current, voltage, resistance; kilo (k, 10³) — voltage, power, resistance; mega (M, 10⁶) — power, resistance. Critical confusion: lowercase 'm' means milli (×0.001) while uppercase 'M' means mega (×1,000,000) — a factor of 10⁹ difference. This distinction has caused real-world component ordering disasters.

Frequency and period conversions connect time-domain and frequency-domain analysis: f (Hz) = 1/T (seconds), ω (rad/s) = 2πf. Power system frequencies: 60 Hz (North America, period = 16.67 ms), 50 Hz (most of the world, period = 20 ms). For AC circuits: impedance is frequency-dependent — capacitive reactance Xc = 1/(2πfC) and inductive reactance XL = 2πfL. Changing frequency from 60 Hz to 50 Hz changes reactance by 17% — significant for capacitor banks, filter circuits, and motor impedance. Angular frequency ω is used in phasor analysis and control system design.

Frequently Asked Questions

What is the most common mistake in unit conversion?

Confusing kW (real power) with kVA (apparent power). They are only equal at unity power factor (PF = 1.0). For a motor with PF = 0.85: kVA = kW / 0.85 — a 10 kW motor draws 11.76 kVA. Sizing a transformer or conductor using kW instead of kVA undersizes it by 18%. The second most common mistake: confusing HP nameplate rating (shaft output) with electrical input — a 10 HP motor at 88% efficiency draws 8.47 kW electrical, not 7.46 kW. Always clarify whether a power specification is input or output, and whether it's kW or kVA.

How do I convert between voltage levels?

Voltage conversion uses transformers. The turn ratio determines the voltage ratio: V_secondary / V_primary = N_secondary / N_primary. Common North American distribution voltages: 4160V → 480/277V (delta-wye), 480V → 208/120V (delta-wye), 240V → 120V (single-phase center-tap). Power is conserved (minus losses): kVA_primary ≈ kVA_secondary. Current scales inversely with voltage: stepping from 480V to 208V increases current by 480/208 = 2.31×. This is why 480V distribution is standard for commercial buildings — lower current means smaller conductors and lower I²R losses.

What is a circular mil?

A circular mil (cmil) is the area of a circle with diameter of 1 mil (0.001 inch). 1 cmil = π/4 × 10⁻⁶ in² = 5.067 × 10⁻⁴ mm². It simplifies area calculations for round conductors: area in cmils = (diameter in mils)² (no π/4 factor needed). 1 kcmil = 1,000 cmils = 0.5067 mm². Examples: 250 kcmil = 250,000 cmils = 126.7 mm², 500 kcmil = 253.4 mm². The cmil system is used exclusively in North American electrical engineering; international practice uses mm² exclusively.

How do I convert BTU to electrical units?

1 BTU = 1,055.06 J = 0.000293 kWh. 1 kWh = 3,412 BTU. For power (rate of energy): 1 BTU/h = 0.293 W, 1 kW = 3,412 BTU/h, 1 ton of refrigeration = 12,000 BTU/h = 3.517 kW. Common confusion: BTU is energy (quantity), BTU/h is power (rate) — but HVAC industry often drops the '/h' and says 'BTU' when they mean BTU/h. A '60,000 BTU' furnace actually means 60,000 BTU/h = 17.6 kW thermal output. Electric equivalent at 100% efficiency: a 17.6 kW electric heater produces identical thermal output.

How do decibels work in electrical engineering?

Decibels (dB) express ratios logarithmically. For power: dB = 10 × log₁₀(P₂/P₁). For voltage/current: dB = 20 × log₁₀(V₂/V₁). Quick references: +3 dB = 2× power (1.41× voltage), +6 dB = 4× power (2× voltage), +10 dB = 10× power (3.16× voltage), +20 dB = 100× power (10× voltage), -3 dB = 0.5× power. dBm references 1 mW: 0 dBm = 1 mW, +30 dBm = 1 W, +60 dBm = 1 kW. Used in telecommunications, signal processing, and power quality (harmonic levels are often expressed in dB relative to fundamental).

What are the most dangerous SI prefix errors?

The most expensive errors involve confusing milli- (m, 10⁻³) with mega- (M, 10⁶) — a 10⁹ (one billion) factor error. 10 mΩ (milliohms) is a near-short-circuit; 10 MΩ (megaohms) is near-open-circuit. Other common errors: confusing μF (microfarad) with pF (picofarad) — 10⁶ difference that determines whether a capacitor bank corrects a building's power factor or does nothing detectable. In handwriting, 'mA' (milliamps) vs 'MA' can be ambiguous — always use clear notation. Digital systems should always include the full prefix name when abbreviation could be ambiguous.

What is the difference between resistance and impedance?

Resistance (R, ohms) is the DC opposition to current flow — purely resistive, independent of frequency. Impedance (Z, ohms) is the total AC opposition including resistance (R), inductive reactance (XL = 2πfL), and capacitive reactance (XC = 1/(2πfC)). Z = √(R² + (XL - XC)²). At DC (f = 0): Z = R. At 60 Hz AC: impedance includes the effects of inductors and capacitors. For power conductors: resistance dominates for small sizes (<2 AWG), while reactance becomes significant for larger conductors (>500 kcmil). NEC Chapter 9, Table 9 provides both R and X values for conductors.

Related Calculators

Authoritative Standards

  • IEEE Std 100 — Authoritative Dictionary of IEEE Standards Terms
  • IEC 60050 — International Electrotechnical Vocabulary
  • NIST SP 811 — Guide for the Use of the International System of Units
  • IEEE 270 — Standard Definitions for Commonly Used Letters and Mathematical Signs

Project Explorer

No Projects Found