Breaker Size and Wire Size Chart

Common breaker-to-wire pairings, with reminders for derating, continuous load and terminal limits.
Source
NEC ampacity and overcurrent data
Edition
2023
Updated
2026-07-27
Scope
United States

Lookup Table

Which breaker and conductor sizes commonly pair together?

BreakerCommon copperCommon aluminumCaution
15 A14 AWG12 AWGSmall-conductor limit
20 A12 AWG10 AWGSmall-conductor limit
30 A10 AWG8 AWGSmall-conductor limit
50 A6 AWG4 AWGTerminal rating often governs
100 A3 AWG1 AWGCheck voltage drop
Breaker Size and Wire Size Chart. Derived as a task-focused reference view; verify marginal work against the source and the AHJ edition.

Calculated against the NEC 2023 edition using 240.4, 240.4(D), 240.6(A), 110.14(C). Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.

Not covered by this tool

  • Local amendments and equipment markings can be stricter than this reference view.
  • Marginal values should be checked directly against the adopted edition.
  • This page is a routing aid and does not replace the owning calculator for project-specific inputs.