Breaker & Wire Size Compatibility Checker
- Code basis
- NEC 2023, Art. 240 / 310
- Editions
- 2017, 2020, 2023
- Checks run
- Up to 6, reported separately
- Verdict
- Pass or fail per rule
- Conductor sizes
- 14 AWG – 1000 kcmil
- Materials
- Copper, aluminum
- Refuses
- Motor, HVAC, welder
Circuit type
Motor, air-conditioning, welder and transformer circuits follow different rules and are refused rather than answered.
Breaker and conductor
Enter what is installed or what you intend to install. Non-standard ratings are flagged rather than rejected.
Conditions and load
Conditions decide the conductor's real ampacity. The load decides whether the breaker is large enough.
Largest permitted breaker
Compatible30 A
Entered: 30 A on 10 AWG copper, 90 °C insulation into 75 °C terminations.
- Checks passed
- 4 of 4
- Conductor ampacity here
- 30 Aafter every correction and cap
- Smallest breaker for the load
- 25 A24 A required
- Grounding conductor
- 10 AWGminimum for this device rating
- A 30 A device requires 10 AWG copper as a minimum grounding conductor. Select the size installed to have it checked.
Every check, individually
Breaker is a standard rating
Pass30 A is a standard rating.
240.6(A)
Conductor is protected at its ampacity
PassThe conductor is good for 30 A under these conditions, so a 30 A breaker protects it.
240.4(B)
Within the small conductor limit
Pass10 AWG copper is capped at 30 A, and 30 A is within it.
240.4(D)
Breaker covers the load
PassA 24 A load is within the 30 A breaker.
210.20(A)
Conductor ampacity
| Step | Basis | Effect | Value |
|---|---|---|---|
| Base ampacity, 10 AWG copper | Table 310.16 | — | 40 A |
| Termination rated 75 C | 110.14(C) | cap 35 | 35 A |
| Small conductor overcurrent limitGoverning | 240.4(D) | cap 30 | 30 A |
The tabulated value is the starting point. Everything below it is a correction, an adjustment or a cap that the breaker rating has to respect.
Calculated against the NEC 2023 edition using Table 310.16, 110.14(C), 240.6(A), 240.4(B), 240.4(D), 210.20(A), Table 250.122. Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.
Not covered by this tool
- Motor, air-conditioning, welder and transformer circuits, which are refused rather than answered.
- Tap conductors, transformer secondary conductors and the other exceptions to the small conductor rule.
- Receptacle rating against branch-circuit rating, which is a separate check on the device rather than on the conductor.
- Ground-fault and arc-fault protection requirements, which are set by the area served rather than by the conductor.
- Series-rated and current-limiting combinations, and available fault current at the equipment.
- Conductors in free air, which are sized from a different ampacity table.
Data last verified
What Gets Checked
Six rules, evaluated independently. A pass on one is not a pass on the others.
Check 1
Standard device rating
Confirms the breaker is a rating that is actually manufactured and listed. A non-standard rating is permitted in limited cases but is rarely what was intended, so it is reported as a caution rather than a failure.
Check 2
Conductor protected at its ampacity
Compares the device rating against the conductor's ampacity after every correction and cap, applying the next-standard-size-up allowance where the circuit qualifies for it.
Check 3
Small conductor limit
Enforces the fixed overcurrent ceilings on 14, 12 and 10 AWG. These override the ampacity table entirely, which is why a 12 AWG conductor with a tabulated 30 A ampacity still cannot be protected above 20 A.
Check 4
Terminal temperature
Caps the conductor at the ampacity in the column matching the lowest-rated termination. Surfaced whenever that cap is what held the number down, because reading the 90 degrees C column alone is the most common way to reach a wrong answer here.
Check 5
Breaker covers the load
Checks the device against the operating current, with the 125 percent multiplier applied when the load is continuous. A breaker can be too small as easily as it can be too large.
Check 6
Grounding conductor size
Compares the installed equipment grounding conductor against the minimum for the device rating. Optional, because the field is frequently unknown at the point someone is checking a breaker.
Every rule is reported on its own line with the numbers that decided it. Knowing the conductor is fine and only the small conductor rule is violated tells you to change the breaker; knowing only that the combination failed tells you nothing.
Breaker Ceiling by Conductor Size
Copper into 75 degrees C terminations, in benign conditions. Correct these downward for ambient temperature and conductor count.
| Size | Ampacity 75 °C | Max breaker | Min. EGC | Typical circuit |
|---|---|---|---|---|
| 14 AWG | 20 | 15 A | 14 AWG | 15 A lighting and receptacle circuits |
| 12 AWG | 25 | 20 A | 12 AWG | 20 A general-purpose and kitchen circuits |
| 10 AWG | 35 | 30 A | 10 AWG | 30 A dryer, water heater, small subpanel |
| 8 AWG | 50 | 50 A | 10 AWG | 40 to 50 A range, EVSE, subpanel feeder |
| 6 AWG | 65 | 60 A | 10 AWG | 50 to 60 A range, hot tub, subpanel feeder |
| 4 AWG | 85 | 80 A | 8 AWG | 70 A subpanel feeder |
| 3 AWG | 100 | 100 A | 8 AWG | 85 A feeder |
| 2 AWG | 115 | 110 A | 6 AWG | 90 to 100 A subpanel feeder |
| 1 AWG | 130 | 125 A | 6 AWG | 100 to 110 A feeder |
| 1/0 AWG | 150 | 150 A | 6 AWG | 125 A feeder |
| 2/0 AWG | 175 | 175 A | 6 AWG | 150 A feeder |
| 3/0 AWG | 200 | 200 A | 6 AWG | 175 to 200 A feeder |
| 4/0 AWG | 230 | 225 A | 4 AWG | 200 A feeder |
These are ceilings in ideal conditions, not answers. An attic at 130 degrees F removes a quarter of the ampacity, and nine conductors in one raceway remove thirty percent. Both are common, and both move the numbers above.
Common Combinations and Their Verdicts
The pairings that come up most, and the condition that flips each one.
| Combination | Verdict | Governing rule |
|---|---|---|
| 30 A breaker on 10 AWG copper | Pass | At the small conductor ceiling exactly. Correct for a dryer or water heater in normal ambient with three conductors in the raceway. |
| 20 A breaker on 14 AWG copper | Fail | 14 AWG cannot be protected above 15 A regardless of its tabulated ampacity. The most frequent real-world violation this tool catches. |
| 50 A breaker on 8 AWG THHN into 75 degrees C lugs | Pass | The 90 degrees C column reads 55 A, but the terminations cap it at 50 A, which the device matches exactly. |
| 60 A breaker on 6 AWG NM cable | Fail | Cable assemblies are limited to the 60 degrees C column, where 6 AWG is 55 A. The same conductor in conduit as THHN passes. |
| 40 A breaker on 8 AWG with nine conductors in the raceway | Fail | The bundling adjustment removes 30 percent of the ampacity. The conductor is compliant on its own and fails in company. |
| 100 A breaker on 4 AWG copper feeding a subpanel | Fail | 4 AWG is 85 A at 75 degrees C. The next-size-up allowance reaches 90 A, not 100 A. Use 3 AWG or larger. |
Circuits This Tool Will Not Judge
Four cases where a general branch-circuit check produces a confidently wrong answer. The tool refuses them instead.
Motors and air conditioning
Branch-circuit protection is selected from the motor tables at a rating normally well above the conductor ampacity, because it guards against short circuit and ground fault while a separate overload device protects the conductor. An ampacity comparison returns a fail on a compliant installation.
Equipment marked with a minimum circuit ampacity
Air conditioners, heat pumps, mini splits and refrigeration equipment carry a marked minimum circuit ampacity and a marked maximum overcurrent device rating. Those markings govern. Size the conductor to the minimum circuit ampacity and set the device at or below the marked maximum.
Welders and transformers
Welder conductors are sized from rated primary current and duty cycle, with overcurrent devices permitted at multiples of that current. Transformer protection depends on what secondary protection is provided. Neither reduces to a conductor-ampacity comparison.
Tap conductors and secondary conductors
Tap rules permit a conductor to be protected at a rating above its own ampacity under stated length and termination conditions. This tool applies the general rule, so a legitimate tap will read as a failure here.
What to Change When a Check Fails
Each failure has a specific remedy. Work from the rule that failed, not from the verdict.
The conductor fails on ampacity
Either fit the largest device the conductor permits, shown in the result panel, or increase the conductor. Increasing insulation temperature rating rarely helps on its own, because the terminations usually cap the result before the insulation does.
The small conductor rule fails
There is no way around it on 14, 12 or 10 AWG. Reduce the device to the stated ceiling or move up a size. The exceptions in that rule cover tap and motor applications, not general branch circuits.
The termination temperature is the cap
Check the equipment label before assuming 75 degrees C. Terminations on equipment rated 100 A or less are treated as 60 degrees C unless marked otherwise, which is what turns a compliant-looking 8 AWG at 50 A into a failure on some panels.
The breaker does not cover the load
Move up to the next standard rating and re-check the conductor against it. A continuous load needs 125 percent of its current available, so a 40 A continuous load requires 50 A of device and a conductor to match.
Conductor count triggered an adjustment
Split the circuits between raceways, or accept the derated ampacity and size up. Counting is where most errors start: three two-wire circuits in one raceway is six current-carrying conductors, and the grounding conductor is never counted.
The grounding conductor is undersized
Size it from the device rating, not from the ungrounded conductors. Where the ungrounded conductors were upsized for voltage drop, increase it proportionally to their increase in circular mil area.