Wire Size & Ampacity Calculator
- Code basis
- NEC 2023, Art. 310 / 240
- Editions
- 2017, 2020, 2023
- Conductor sizes
- 14 AWG – 1000 kcmil
- Materials
- Copper, aluminum
- Constraints
- Ampacity, OCPD, voltage drop
Circuit details
Every field affects the result. Defaults describe a common 240 V branch circuit.
Minimum conductor
Pass8 AWG
Governed by the temperature rating of the terminations.
- Derated ampacity
- 50 ARequired: 40 A
- Overcurrent device
- 40 A
- Grounding conductor
- 10 AWG
- Voltage drop
- 1.9%4.7 V lost, 235 V at the load
Required current
| Step | Basis | Effect | Value |
|---|---|---|---|
| Load current | — | — | 40 A |
Conductor ampacity
| Step | Basis | Effect | Value |
|---|---|---|---|
| Base ampacity, 8 AWG copper | Table 310.16 | — | 55 A |
| Termination rated 75 CGoverning | 110.14(C) | cap 50 | 50 A |
Calculated against the NEC 2023 edition using 310.16, 310.15(B)(1), 310.15(C)(1), 110.14(C), 240.4, 250.122. Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.
Not covered by this tool
- Conductors in free air, which are sized from a different ampacity table.
- Raceways exposed to direct sunlight on or above a rooftop.
- Motor and air-conditioning circuits, which have their own sizing rules.
- Parallel conductor sets and taps.
Data last verified
Calculation Method
Six steps, in the order the code applies them.
Step 1
Required current
A continuous load is taken at 125 percent; a non-continuous load at its actual current.
Step 2
Tabulated ampacity
Read from the column matching the conductor insulation, based on 30 degrees C ambient and no more than three current-carrying conductors.
Step 3
Ambient correction
Multiplied by the correction factor for the actual ambient temperature. Above the published range the conductor is not permitted, and no extrapolation is performed.
Step 4
Bundling adjustment
Multiplied by the adjustment factor for the number of current-carrying conductors in the raceway: 80 percent for four to six, 50 percent for ten to twenty.
Step 5
Termination limit
Capped at the ampacity in the column matching the lowest-rated termination. This is a cap, not a multiplier, and does not enter the preceding arithmetic.
Step 6
Overcurrent and voltage drop
The device is selected from the standard ratings subject to the small-conductor limits and the next-size-up allowance. If drop over the run exceeds the target, the conductor is upsized and the result is reported as drop-governed.
The equipment grounding conductor is sized from the overcurrent device rating, not from the ungrounded conductors. Where the ungrounded conductors are upsized for voltage drop, the grounding conductor must be increased proportionally.
Governing Constraint by Scenario
The binding constraint varies by installation, which is why a single lookup table cannot answer this.
| Scenario | Usually governed by | Basis |
|---|---|---|
| Short 20 A receptacle circuit in conditioned space | Small conductor overcurrent limit | The table allows more, but 12 AWG cannot be protected above 20 A. |
| 50 A range feeder, 30 ft, three conductors | Termination temperature | The 90 C column reads higher, but the 75 C lugs set the ceiling. |
| Six circuits sharing one raceway in an attic | Ambient correction and bundling adjustment together | Compounding 0.91 and 0.80 removes over a quarter of the ampacity. |
| 20 A circuit to a detached garage, 200 ft | Voltage drop | Ampacity allows 12 AWG; staying under 3 percent needs 8 AWG. |
| 200 A aluminum service conductors | Tabulated ampacity | Conditions are benign, so the table value decides it directly. |
Ampacity Reference
Tabulated values before correction. The calculator applies ambient and bundling factors; this table does not.
| Size | Cu 60 °C | Cu 75 °C | Cu 90 °C | Al 75 °C | Max breaker |
|---|---|---|---|---|---|
| 14 AWG | 15 | 20 | 25 | — | 15 A |
| 12 AWG | 20 | 25 | 30 | 20 | 20 A |
| 10 AWG | 30 | 35 | 40 | 30 | 30 A |
| 8 AWG | 40 | 50 | 55 | 40 | By ampacity |
| 6 AWG | 55 | 65 | 75 | 50 | By ampacity |
| 4 AWG | 70 | 85 | 95 | 65 | By ampacity |
| 3 AWG | 85 | 100 | 115 | 75 | By ampacity |
| 2 AWG | 95 | 115 | 130 | 90 | By ampacity |
| 1 AWG | 110 | 130 | 145 | 100 | By ampacity |
| 1/0 AWG | 125 | 150 | 170 | 120 | By ampacity |
| 2/0 AWG | 145 | 175 | 195 | 135 | By ampacity |
| 3/0 AWG | 165 | 200 | 225 | 155 | By ampacity |
| 4/0 AWG | 195 | 230 | 260 | 180 | By ampacity |
Input Guidance
The four fields most often entered incorrectly.
Ambient temperature
Use the air temperature surrounding the raceway, not the room setpoint. Attics, boiler rooms and south-facing exterior walls sit well above the 86 degrees F the tables assume. An optimistic value here is the most consequential input error on this page.
Current-carrying conductors
Count only conductors carrying current. On a single-phase multiwire branch circuit the neutral carries unbalanced current only and is excluded; the equipment grounding conductor is always excluded. Three two-wire circuits in one raceway is six current-carrying conductors, not nine.
Termination rating
Use the lower rating of the two ends. Equipment listed for 75 degrees C is typical, but unless marked otherwise, terminations on equipment rated 100 amperes or less are treated as 60 degrees C. Verify against the equipment label.
Conductor material
Aluminum requires roughly one to two sizes more than copper for the same load at significantly lower cost. It is standard for services and large feeders and uncommon for branch circuits. Confirm terminations are listed for aluminum before specifying it.