NEC 310.16 Ampacity Chart with Derating Applied
- Code basis
- NEC 2023, Art. 310
- Editions
- 2017, 2020, 2023
- Sizes
- 14 AWG – 1000 kcmil
- Rows
- 24 copper, 23 aluminum
- Columns
- 60 / 75 / 90 °C
- Corrections
- Ambient, conductor count
- Caps applied
- Termination, 240.4(D)
Conditions of use
Defaults match the table's own basis: 86 degrees F and three current-carrying conductors. Change them to see what the conductors are actually good for.
Smallest size that carries the load
Pass6 AWG
65 A usable against 60 A required.
- Tabulated ampacity
- 75 A90 °C column
- Combined derating
- × 1.0001 ambient, 1 conductor count
- Governing limit
- Termination rating110.14(C)
- Max overcurrent device
- 60 AStandard rating at or below the usable ampacity
| Size | Table, 90 °C | Usable | Governing limit | Basis | Max OCPD | vs 60 A |
|---|---|---|---|---|---|---|
| 14 AWG | 25 | 15 | Small conductor limit | 240.4(D) | 15 A | −45 |
| 12 AWG | 30 | 20 | Small conductor limit | 240.4(D) | 20 A | −40 |
| 10 AWG | 40 | 30 | Small conductor limit | 240.4(D) | 30 A | −30 |
| 8 AWG | 55 | 50 | Termination rating | 110.14(C) | 50 A | −10 |
| 6 AWG | 75 | 65 | Termination rating | 110.14(C) | 60 A | +5 |
| 4 AWG | 95 | 85 | Termination rating | 110.14(C) | 80 A | +25 |
| 3 AWG | 115 | 100 | Termination rating | 110.14(C) | 100 A | +40 |
| 2 AWG | 130 | 115 | Termination rating | 110.14(C) | 110 A | +55 |
| 1 AWG | 145 | 130 | Termination rating | 110.14(C) | 125 A | +70 |
| 1/0 AWG | 170 | 150 | Termination rating | 110.14(C) | 150 A | +90 |
| 2/0 AWG | 195 | 175 | Termination rating | 110.14(C) | 175 A | +115 |
| 3/0 AWG | 225 | 200 | Termination rating | 110.14(C) | 200 A | +140 |
| 4/0 AWG | 260 | 230 | Termination rating | 110.14(C) | 225 A | +170 |
| 250 kcmil | 290 | 255 | Termination rating | 110.14(C) | 250 A | +195 |
| 300 kcmil | 320 | 285 | Termination rating | 110.14(C) | 250 A | +225 |
| 350 kcmil | 350 | 310 | Termination rating | 110.14(C) | 300 A | +250 |
| 400 kcmil | 380 | 335 | Termination rating | 110.14(C) | 300 A | +275 |
| 500 kcmil | 430 | 380 | Termination rating | 110.14(C) | 350 A | +320 |
| 600 kcmil | 475 | 420 | Termination rating | 110.14(C) | 400 A | +360 |
| 700 kcmil | 520 | 460 | Termination rating | 110.14(C) | 450 A | +400 |
| 750 kcmil | 535 | 475 | Termination rating | 110.14(C) | 450 A | +415 |
| 800 kcmil | 555 | 490 | Termination rating | 110.14(C) | 450 A | +430 |
| 900 kcmil | 585 | 520 | Termination rating | 110.14(C) | 500 A | +460 |
| 1000 kcmil | 615 | 545 | Termination rating | 110.14(C) | 500 A | +485 |
How 6 AWG reaches 65 A
| Step | Basis | Effect | Value |
|---|---|---|---|
| Base ampacity, 6 AWG copper | Table 310.16 | — | 75 A |
| Termination rated 75 CGoverning | 110.14(C) | cap 65 | 65 A |
Calculated against the NEC 2023 edition using 310.16, 310.15(B)(1), 310.15(C)(1), 110.14(C), 240.4(D), 240.6(A). Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.
Not covered by this tool
- Conductors in free air, which are tabulated separately.
- Raceways exposed to direct sunlight on or above a rooftop.
- Motor, air-conditioning and welder circuits, which have their own sizing rules.
- Parallel conductor sets, taps and the exceptions that waive the conductor count adjustment.
- Voltage drop, which is independent of ampacity and often governs a long run.
Data last verified
How the Usable Value Is Built
Four steps, in the order the code applies them.
Step 1
Read the column for the insulation
The insulation temperature rating selects the column: 90 degrees C for THHN and XHHW-2, 75 for THWN and wet-location XHHW, 60 for TW. The termination rating does not select the column.
Step 2
Correct for ambient temperature
Multiply by the factor for the actual ambient temperature in that column. Above the tabulated range the conductor is not permitted, and this page returns no value rather than extrapolating.
Step 3
Adjust for conductor count
Multiply by the factor for the current-carrying conductors sharing the raceway: 80 percent for four to six, 70 percent for seven to nine, 50 percent for ten to twenty.
Step 4
Apply the ceilings
Cap the result at the table value in the termination's column, then at the small conductor overcurrent limit on 14, 12 and 10 AWG. Ceilings apply after the multipliers, never before.
Corrections multiply and ceilings cap. Applying the termination ceiling before the multipliers is the most common arithmetic error in conductor sizing, and it understates the conductor by up to a full size on 90 degree C insulation.
What Conditions Do to 8 AWG Copper
One conductor, five installations. Every figure is computed by the same engine as the calculators, from the 90 degree C column onto 75 degree C terminations.
| Installation | Ambient | Current-carrying | Usable ampacity | Governing limit |
|---|---|---|---|---|
| Conditioned space, single circuit | 86 °F | 3 | 50 A | Termination rating |
| Three circuits sharing one raceway | 86 °F | 6 | 44 A | Conductor count |
| Unconditioned attic, single circuit | 113 °F | 3 | 47.9 A | Ambient correction |
| Three circuits in an attic raceway | 104 °F | 6 | 40 A | Conductor count |
| Five circuits sharing one raceway | 86 °F | 10 | 27.5 A | Conductor count |
The tabulated 90 degree C value for 8 AWG copper is 55 A. Nothing in the list reaches it: the termination rating alone holds the best case to 50 A, and ten conductors in one raceway leave 27.5 A. A chart that reports 55 A is answering a question nobody is asking.
Copper Against Aluminum by Breaker Rating
Minimum size at 86 degrees F, three current-carrying conductors, 75 degree C insulation and 75 degree C terminations.
| Breaker | Copper | Aluminum | Aluminum penalty |
|---|---|---|---|
| 20 A | 12 AWG | 10 AWG | 1 size larger |
| 30 A | 10 AWG | 8 AWG | 1 size larger |
| 40 A | 8 AWG | 8 AWG | Same size |
| 50 A | 8 AWG | 6 AWG | 1 size larger |
| 60 A | 6 AWG | 4 AWG | 1 size larger |
| 70 A | 4 AWG | 3 AWG | 1 size larger |
| 80 A | 4 AWG | 2 AWG | 2 sizes larger |
| 90 A | 3 AWG | 2 AWG | 1 size larger |
| 100 A | 3 AWG | 1 AWG | 2 sizes larger |
| 125 A | 1 AWG | 2/0 AWG | 2 sizes larger |
| 150 A | 1/0 AWG | 3/0 AWG | 2 sizes larger |
| 175 A | 2/0 AWG | 4/0 AWG | 2 sizes larger |
| 200 A | 3/0 AWG | 250 kcmil | 2 sizes larger |
Aluminum runs one to two sizes larger for the same rating at a fraction of the material cost, which is why it is standard for services and large feeders. Terminations must be listed for aluminum, and the change in size also changes conduit fill and the equipment grounding conductor.
Reading the Right Column
Four decisions that change the answer more than the conductor size does.
Match the column to the insulation, not the breaker
A THHN conductor is read from the 90 degree C column even on 75 degree C lugs. Reading the 75 degree C column from the start and then derating it produces a smaller answer than the code requires and quietly wastes a size on long feeders.
Assume the lower termination rating unless marked
Equipment rated 100 A or less is treated as having 60 degree C terminations unless it is marked otherwise, and larger equipment as 75. Set the termination field from the equipment label, because on small conductors this cap governs more often than derating does.
Use the 60 degree C column for cable assemblies
Nonmetallic-sheathed cable is limited to the 60 degree C column by its own article regardless of the conductor insulation inside it, so a 12 AWG NM cable is a 20 A conductor. Select TW to read that column here, and confirm against the article covering the cable type.
Leave the chart when the run is long
Ampacity is a thermal limit and is independent of length. Beyond roughly 100 feet at branch-circuit voltages, voltage drop governs the size more often than ampacity does, and no ampacity chart will show it.
Source and Attribution
What this page derives from, and what it deliberately is not.
Numeric values on this page derive from NFPA 70, National Electrical Code, 2023 edition, the ampacity table for conductors rated 0 to 2000 V, together with the ambient correction factors, the adjustment factors for more than three current-carrying conductors, the termination temperature limitation and the standard overcurrent device ratings. The authoritative text is the published code. NFPA provides free read-only access at nfpa.org/freeaccess.
This page is not a reproduction of the published table. It reorganises the values into a task-shaped view, applies the corrections and ceilings for conditions the reader supplies, and reports derived figures that the printed table does not contain. No code text, section wording, or informational note is reproduced here.
NEC®, National Electrical Code® and NFPA 70® are registered trademarks of the National Fire Protection Association. ElectraKit is not affiliated with, endorsed by, or sponsored by NFPA. Confirm the edition your authority having jurisdiction enforces, and any local amendments, before relying on a result.