Insulated Conductor Dimensions
Common insulated-conductor dimensions used by the conduit fill engine.
- Source
- Chapter 9 Table 5 and Table 5A
- Edition
- 2023
- Updated
- 2026-07-27
- Scope
- United States
Lookup Table
Which conductor area is used in conduit fill?
| Size | THHN / THWN-2 | XHHW-2 | Use |
|---|---|---|---|
| 12 AWG | 0.0133 sq in | 0.0181 sq in | Branch circuits |
| 10 AWG | 0.0211 sq in | 0.0243 sq in | Branch circuits |
| 6 AWG | 0.0507 sq in | 0.0590 sq in | Feeders |
| 2 AWG | 0.1158 sq in | 0.1333 sq in | Feeders |
Calculated against the NEC 2023 edition using Chapter 9 Table 5, Chapter 9 Table 5A. Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.
Not covered by this tool
- Local amendments and equipment markings can be stricter than this reference view.
- Marginal values should be checked directly against the adopted edition.
- This page is a routing aid and does not replace the owning calculator for project-specific inputs.