Conduit Fill Limits by Conductor Count
The one, two, three-or-more and short-nipple fill limits used by the conduit fill calculator.
- Source
- Chapter 9 Table 1
- Edition
- 2023
- Updated
- 2026-07-27
- Scope
- United States
Lookup Table
Which fill percentage applies to this raceway?
| Conductors | Permitted fill | Use |
|---|---|---|
| 1 | 53% | Single conductor in a raceway |
| 2 | 31% | Most restrictive packing case |
| 3 or more | 40% | Most branch and feeder pulls |
| Nipple <= 24 in | 60% | Short nipple between enclosures |
Calculated against the NEC 2023 edition using Chapter 9 Table 1. Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.
Not covered by this tool
- Local amendments and equipment markings can be stricter than this reference view.
- Marginal values should be checked directly against the adopted edition.
- This page is a routing aid and does not replace the owning calculator for project-specific inputs.