Skip to content

EMT Conduit Fill Chart

EMT trade-size areas and the 40 percent fill column used for multi-conductor pulls.
Source
Chapter 9 Table 4
Edition
2023
Updated
2026-07-27
Scope
United States

Lookup Table

How much area is available in EMT conduit?

EMT trade sizeTotal area40% area
1/2 in0.304 sq in0.122 sq in
3/4 in0.533 sq in0.213 sq in
1 in0.864 sq in0.346 sq in
1-1/4 in1.496 sq in0.598 sq in
1-1/2 in2.036 sq in0.814 sq in
2 in3.356 sq in1.342 sq in
EMT Conduit Fill Chart. Derived as a task-focused reference view; verify marginal work against the source and the AHJ edition.

Calculated against the NEC 2023 edition using Chapter 9 Table 4, Chapter 9 Table 1. Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.

Not covered by this tool

  • Local amendments and equipment markings can be stricter than this reference view.
  • Marginal values should be checked directly against the adopted edition.
  • This page is a routing aid and does not replace the owning calculator for project-specific inputs.

Data last verified