Skip to content

PVC Schedule 40 Conduit Fill Chart

PVC Schedule 40 areas and fill limits for common branch and feeder pulls.
Source
Chapter 9 Table 4
Edition
2023
Updated
2026-07-27
Scope
United States

Lookup Table

How much area is available in PVC Schedule 40 conduit?

PVC trade sizeTotal area40% area
1/2 in0.285 sq in0.114 sq in
3/4 in0.508 sq in0.203 sq in
1 in0.832 sq in0.333 sq in
1-1/4 in1.453 sq in0.581 sq in
1-1/2 in1.986 sq in0.794 sq in
2 in3.291 sq in1.316 sq in
PVC Schedule 40 Conduit Fill Chart. Derived as a task-focused reference view; verify marginal work against the source and the AHJ edition.

Calculated against the NEC 2023 edition using Chapter 9 Table 4, Chapter 9 Table 1. Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.

Not covered by this tool

  • Local amendments and equipment markings can be stricter than this reference view.
  • Marginal values should be checked directly against the adopted edition.
  • This page is a routing aid and does not replace the owning calculator for project-specific inputs.

Data last verified