Intermediate

Capacitor kVAR Sizing Formula

Size power factor correction capacitors — calculate required kVAR from existing and target power factor.

Formulas

kVAR = kW × (tan φ₁ − tan φ₂)

Required capacitor kVAR

φ = arccos(PF)

Phase angle from power factor

Variable Definitions

kVAR=Required capacitor reactive power(kVAR)
kW=Real power of load(kilowatts)
φ₁=Current power factor angle(degrees)
φ₂=Target power factor angle(degrees)
PF=Power factor(dimensionless (0-1))

Worked Example

400 kW load at 0.72 PF, correct to 0.95 PF.

  1. φ₁ = arccos(0.72) = 43.95°, tan(43.95°) = 0.964
  2. φ₂ = arccos(0.95) = 18.19°, tan(18.19°) = 0.329
  3. kVAR = 400 × (0.964 − 0.329) = 400 × 0.635 = 254 kVAR

Answer: 254 kVAR capacitor bank needed (select 250 or 300 kVAR standard)

When to Use

  • Sizing power factor correction capacitor banks
  • Reducing utility power factor penalties
  • Freeing transformer and feeder capacity by reducing reactive power
  • Meeting utility PF requirements (typically >0.90)

Standards & References

  • NEC 460 — Capacitors
  • NEC 460.8 — Disconnect rated at 135% of capacitor current
  • IEEE 1036 — Shunt Power Capacitor Application

Project Explorer

No Projects Found