Voltage Drop: Voltage Lost Over Distance
Voltage drop is the reduction in voltage between the source and the load caused by current flowing through conductor resistance or impedance over the circuit length.
Voltage drop gets confused with ampacity, breaker sizing and code failure. In this site's public calculator it is mainly a design-performance check: lost volts are estimated from operating current, conductor resistance, one-way length, nominal voltage and phase.
How the calculation works
The public calculator uses conductor resistance in ohms per 1000 feet, operating current, one-way length, nominal voltage and the phase multiplier.
Table 9 impedance is not described as a live public method unless that data path is verified and exposed by the calculator.
How to read the targets
The familiar branch-circuit and combined percentages come from informational notes, so an over-target result is reported as a caution rather than an automatic NEC violation.
That wording still leaves room for stricter project requirements from local amendments, equipment listings, utility rules or other applicable standards.
What changes after upsizing
Upsizing for drop can change terminations, raceway fill, pulling difficulty and equipment grounding conductor sizing.
After choosing a larger conductor, rerun the ampacity, breaker compatibility and conduit-fill checks so the fix does not create a different installation problem.
Where the Term Decides Something
Four points in the work where the figure is the answer to a question, not vocabulary.
Long branch circuits
A receptacle, lighting, pump or EVSE branch circuit can pass ampacity while arriving several volts low at the load.
Feeder planning
A feeder may consume part of the combined voltage-drop target, leaving less drop budget for downstream branch circuits.
Material comparison
Copper and aluminum can both be valid choices, but their resistance differs enough that long feeders should be checked before conductors are bought.
EGC review after upsizing
When ungrounded conductors are increased for voltage drop, the wire-type equipment grounding conductor may need proportional review.
Which Figure to Use
Reading the term correctly in practice.
Use operating current
Voltage drop follows the current actually flowing, not the breaker handle. Use sustained load current unless the load really operates at the breaker rating.
Enter one-way length
Use the routed conductor distance from source to load. The single-phase and three-phase multipliers account for the circuit path.
Set voltage and phase first
The same amperes cause a larger percentage drop at 120 V than at 240 V, and three-phase uses a different multiplier than single-phase.
Treat targets conservatively
The 3 percent and 5 percent figures are recommendations for most NEC work. Equipment instructions, energy codes or the AHJ can set a tighter project limit.
FAQs
Is exceeding 3 percent voltage drop an NEC violation?
Should voltage drop be calculated from breaker size?
Do I enter round-trip distance?
Can voltage drop require a larger conductor than ampacity?
Calculated against the NEC 2023 edition using Chapter 9 Table 8, 210.19(A) Informational Note, 215.2(A) Informational Note, 250.122(B). Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.
Not covered by this tool
- Mandatory voltage limits set by equipment instructions, utilities, project specifications or non-NEC standards.
- Motor starting voltage, harmonic heating and detailed power-quality analysis.
- Fault-current, short-circuit and coordination studies.
Data last verified