BeginnerUpdated 2026-02-25

Essential Electrician Exam Formulas & Quick Reference

Must-know formulas for journeyman and master electrician exams — Ohm's law, power formulas, NEC calculations, and motor circuit sizing in one guide.

Quick Answer

Core exam formulas: Ohm's Law (V = I × R), Power (P = V × I), Three-Phase Power (P = V × I × √3 × PF), Voltage Drop (VD = 2LIR/1000), Motor Conductor (125% × FLC from Table 430.250), Breaker Sizing (125% for continuous loads), Conduit Fill (40% for 3+ conductors), Transformer kVA (I = kVA × 1000 / V × √3).

Ohm's Law & Power Formulas

Ohm's Law: V = I × R | I = V / R | R = V / I. These three relationships are the foundation of all electrical calculations. Voltage (V) in volts, Current (I) in amps, Resistance (R) in ohms.

Power (Watt's Law): P = V × I | P = I² × R | P = V² / R. Power (P) in watts. These formulas apply to DC circuits and purely resistive AC circuits.

Three-Phase Power: P = V_LL × I_L × √3 × PF (line values) | P = 3 × V_Ph × I_Ph × PF (phase values). Where √3 = 1.732, V_LL = line-to-line voltage, I_L = line current, PF = power factor.

Power Triangle: Apparent Power (kVA) = √(kW² + kVAR²). Power Factor = kW / kVA = cos θ. Reactive Power (kVAR) = kVA × sin θ.

NEC Conductor Sizing

Branch circuit conductors: minimum ampacity ≥ 125% of continuous load + 100% of non-continuous load (NEC 210.19(A)).

Motor conductors: minimum ampacity ≥ 125% of motor FLC from Table 430.248/250 (NEC 430.22).

Feeder for multiple motors: 125% of largest motor FLC + sum of all other motor FLCs (NEC 430.24).

Voltage drop: VD = 2 × L × I × R / 1000 (single-phase) | VD = √3 × L × I × R / 1000 (three-phase). Target ≤ 3% branch, ≤ 5% total.

Overcurrent Protection

Standard breaker sizes: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200A (NEC 240.6(A)).

Small conductor limits: 14 AWG = 15A max, 12 AWG = 20A max, 10 AWG = 30A max (NEC 240.4(D)).

Motor SCGF (inverse-time breaker): max 250% of FLC. If motor won't start, may increase to 400% (NEC 430.52).

Motor SCGF (dual-element fuse): max 175% of FLC. May increase to 225% (NEC 430.52).

Transformer protection: >9A primary → max 125%. ≤9A → max 167%. ≤2A → max 300% (NEC Table 450.3(B)).

Conduit Fill & Box Fill

Conduit fill: 1 conductor = 53%, 2 conductors = 31%, 3+ conductors = 40% of conduit area.

Nipple exception: conduits ≤ 24 inches may be filled to 60%.

Box fill (NEC 314.16(B)): each 14 AWG conductor = 2.0 in³, 12 AWG = 2.25 in³, 10 AWG = 2.5 in³, 8 AWG = 3.0 in³, 6 AWG = 5.0 in³.

Box fill additions: clamps = 1 × largest conductor volume, fixture studs = 1 × largest, devices = 2 × largest, all grounds = 1 × largest.

Residential Load Calculations

General lighting: 3 VA/ft² × square footage.

Small appliance circuits: 2 × 1,500 VA = 3,000 VA minimum.

Laundry circuit: 1 × 1,500 VA.

Demand factors (Table 220.42): first 3,000 VA at 100%, remainder at 35%.

Range: Table 220.55 — single range ≤ 12 kW → use 8 kW.

Dryer: 5,000 VA or nameplate, whichever is larger.

HVAC: use the larger of heating or cooling load (NEC 220.60).

Service sizing: total demand VA ÷ 240V = minimum service amps.

Quick Reference Values

1 HP = 746 watts. 1 ton (HVAC) ≈ 12,000 BTU/hr ≈ 3.517 kW.

Transformer primary-secondary current: I₁/I₂ = V₂/V₁ = N₂/N₁ (inverse voltage ratio).

Three-phase line vs phase: V_LL = V_Ph × √3 (wye). I_L = I_Ph (wye). V_LL = V_Ph (delta). I_L = I_Ph × √3 (delta).

Efficiency: η = (output power / input power) × 100%. Motor input = HP × 746 / η.

Temperature conversion: °F = (°C × 9/5) + 32. °C = (°F - 32) × 5/9.

Calculate Now

Related Guides

Frequently Asked Questions

What is the most important formula for the electrician exam?

Ohm's Law (V = I × R) and its power variations (P = V × I) appear in more exam questions than any other formula. Master these and their rearrangements first. The second most important set of formulas involves NEC calculation methods: conductor sizing (125%), motor circuit rules, and residential load calculations.

How do I calculate three-phase current from kVA?

I = kVA × 1000 / (V × √3). For a 225 kVA transformer at 480V: I = 225,000 / (480 × 1.732) = 270.6A. At 208V: I = 225,000 / (208 × 1.732) = 624.7A. This formula is used frequently for transformer and panel sizing questions.

What is the power factor formula?

PF = kW / kVA = cos θ. Where θ is the phase angle between voltage and current. PF ranges from 0 to 1.0. Unity PF (1.0) means all power is real (resistive). Low PF (0.7-0.8) means significant reactive power from motors and inductors. kVAR = kVA × sin θ.

NEC References

  • NEC 210 — Branch Circuits
  • NEC 220 — Load Calculations
  • NEC 240 — Overcurrent Protection
  • NEC 310 — Conductors
  • NEC 430 — Motors

Project Explorer

No Projects Found