Permit Load Calculation Submittal
- Code basis
- 220.82 / 220.83
- Goal
- Reviewable arithmetic
- Must name
- Edition and jurisdiction
- Avoid
- Bare amp answer only
The Procedure
5 steps, in the order the code applies them.
Step 1
State edition and address
Name the NEC edition adopted by the AHJ and the project address so the reviewer knows which rules you used.
Step 2
Show floor area and circuit allowances
List general lighting area basis plus small-appliance and laundry circuit allowances as separate lines.
Step 3
Itemize appliances and EVSE
Include nameplate values and the EVSE treatment used. Hidden round numbers are where reviews stall.
Step 4
Show demand factors and HVAC selection
Leave the demand-factor arithmetic visible, and show which heating or cooling item was carried forward.
Step 5
Convert to amperes and requested service size
End with VA, amperes at service voltage, and the standard service size you are requesting.
Show the arithmetic
A submittal should show floor area, branch-circuit allowances, appliance nameplates, EVSE treatment, demand factors and the selected heating or cooling item.
A bare service-size answer gives the reviewer no way to find the input that governed the result.
Use the AHJ edition
The permit packet should name the edition and jurisdiction used. Local forms may ask for fields that a national calculator cannot know.
Print or export the line-item calculation with the project address so the review trail stays attached to the job.
Decision Guide
The choices that change the answer, and how to make them.
Match the local form when one exists
Some jurisdictions publish a worksheet. Mirror its line order even if your internal calculator uses a different layout.
Keep inputs editable
Reviewers ask what-if questions. A calculation you cannot adjust in five minutes becomes a delay.
Separate branch-circuit sheets from service calc
EVSE or range branch-circuit worksheets support the install but are not a substitute for the dwelling service calculation.
FAQs
What should a permit load calculation include?
Why do inspectors reject a one-line service size?
Should I submit optional and standard method both?
Calculated against the NEC 2023 edition using 220.82, 220.83, 230.79(C). Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.
Not covered by this tool
- Motor, air-conditioning and welder circuits, which are sized under their own articles.
- Conductors in free air and photovoltaic circuits.
- Parallel conductor sets, taps and busbars.
- Local amendments, which can be stricter than the published code.
Data last verified