Subpanel Feeder Sizing
- Code basis
- 215.2(A)(1), 310.16
- Also check
- Voltage drop, 250.122
- Start from
- Feeder load, not bus rating
- Common miss
- Outbuilding voltage drop
The Procedure
5 steps, in the order the code applies them.
Step 1
Establish the feeder load
Calculate or measure the load the subpanel will supply. The subpanel bus rating is a maximum, not the design current.
Step 2
Size ungrounded conductors
Run ampacity with ambient, bundling and termination inputs for the feeder material you intend to pull.
Step 3
Check voltage drop for the route length
Garage and ADU feeders often upsize here. If drop governs, enlarge the ungrounded conductors and revisit grounding conductor proportion.
Step 4
Size the raceway for the final conductors
After any drop-driven upsize, recalculate conduit fill. Do not lock EMT size from the first ampacity pass.
Step 5
Select the feeder breaker and landings
Confirm the supply-end breaker protects the feeder conductors and that both panels accept the conductor material and size.
Work from load to installation
Start with the feeder load, not the panel's maximum bus rating. Then size the conductor, check the drop and check the raceway.
If voltage drop upsizes the ungrounded conductors, the equipment grounding conductor needs proportional review.
Separate neutral and grounding decisions
Feeder neutrals and equipment grounding conductors are governed by different rules.
Bonding details and service-equipment decisions need project-specific review beyond feeder ampacity.
Decision Guide
The choices that change the answer, and how to make them.
Bus rating ≠ feeder size
A 125 A subpanel can be fed by a smaller feeder when the calculated load is smaller and the installation allows it. Conversely, a large bus does not authorize an undersized feeder.
Neutral and EGC are different rules
Feeder neutrals and equipment grounding conductors follow different sections. Upsizing hots for drop can require EGC review under 250.122.
Outbuildings reopen bonding questions
Separate structures have grounding and bonding requirements beyond feeder ampacity. Resolve them as part of the design, not as punch-list work.
FAQs
How do I size a feeder to a subpanel?
Can I feed a 125 amp subpanel with a 60 amp breaker?
Does voltage drop matter on subpanel feeders?
Calculated against the NEC 2023 edition using 215.2(A)(1), 310.16, 250.122. Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.
Not covered by this tool
- Motor, air-conditioning and welder circuits, which are sized under their own articles.
- Conductors in free air and photovoltaic circuits.
- Parallel conductor sets, taps and busbars.
- Local amendments, which can be stricter than the published code.