Conductor Derating Explained
- Code basis
- 310.15(B)(1), 310.15(C)(1)
- Multipliers
- Ambient × bundling
- Final limit
- 110.14(C) cap
- Common trap
- Capping before derating
The Procedure
5 steps, in the order the code applies them.
Step 1
Read the insulation column
Start from the ampacity column that matches the conductor insulation, not the termination. THHN usually starts in the 90 C column even when the lugs are 75 C.
Step 2
Multiply by ambient correction
Apply the factor for the air temperature around the raceway. Attics and exterior walls often sit well above the 30 C table basis.
Step 3
Multiply by conductor-count adjustment
Count current-carrying conductors in the raceway. Four to six use 80 percent; ten to twenty use 50 percent. The equipment grounding conductor does not count.
Step 4
Cap at the termination rating
After both multipliers, the result may not exceed the table value in the lowest terminal-temperature column at either end.
Step 5
Compare usable ampacity to design current
If the derated and capped value is below the design current, upsize the conductor or reduce the factors by splitting the pull.
Two multipliers, then a cap
Derating starts with the ampacity column for the conductor insulation. Ambient temperature and the conductor-count adjustment multiply that value.
The terminal temperature rule is different. It caps the final result after the multipliers, so applying it first can undersize the conductor.
The count is not the fill count
Derating counts current-carrying conductors. Conduit fill counts all conductors in the raceway, including the EGC.
A pull can pass fill and still require upsizing from derating, or fail fill while the ampacity calculation is still comfortable.
Decision Guide
The choices that change the answer, and how to make them.
Do not apply the terminal cap first
Capping before ambient and bundling factors produces a smaller answer than the procedure requires and fails a plan review that checks the arithmetic.
Derating count is not fill count
Derating counts current-carrying conductors. Fill counts every conductor, including the EGC. A pull can pass fill and still need an upsize from derating.
When to split the raceway instead
When two factors compound below about 0.7, splitting conductors into a second raceway often restores ampacity cheaper than jumping a conductor size.
FAQs
Why did derating make my wire larger than the ampacity chart?
Does the equipment grounding conductor count for derating?
Should I derate from the 75 C or 90 C column?
Calculated against the NEC 2023 edition using 310.15(B)(1), 310.15(C)(1), 110.14(C). Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.
Not covered by this tool
- Motor, air-conditioning and welder circuits, which are sized under their own articles.
- Conductors in free air and photovoltaic circuits.
- Parallel conductor sets, taps and busbars.
- Local amendments, which can be stricter than the published code.
Data last verified