Advanced6 steps

Motor Control Center Design (480V)

Design a 480V motor control center — feeder sizing, individual motor branch circuits, SCGF coordination, and fault current verification.

Scenario Overview

Design a motor control center (MCC) serving five motors in an industrial facility. Size the feeder, branch circuits, overloads, and SCGF protection per NEC 430.

Given Information

  • 5 motors on 480V, 3-phase service
  • Motor 1: 50 HP (FLC = 65A)
  • Motor 2: 25 HP (FLC = 34A)
  • Motor 3: 15 HP (FLC = 21A)
  • Motor 4: 10 HP (FLC = 14A)
  • Motor 5: 7.5 HP (FLC = 11A)
  • Available fault current at MCC: 25 kAIC
  • All motors: SF = 1.15, inverse-time breakers

Calculation Steps

1

Size Individual Motor Branch Conductors

NEC 430.22: conductor ≥ 125% of FLC.

M1: 65 × 1.25 = 81.3A → 3 AWG copper (100A) or 1 AWG aluminum

M2: 34 × 1.25 = 42.5A → 8 AWG copper (50A)

M3: 21 × 1.25 = 26.3A → 10 AWG copper (35A)

M4: 14 × 1.25 = 17.5A → 14 AWG copper (20A)

M5: 11 × 1.25 = 13.8A → 14 AWG copper (20A)

Result: Individual conductors sized: 3, 8, 10, 14, 14 AWG Cu

2

Size Branch Circuit SCGF (Breakers)

NEC 430.52: inverse-time breaker max = 250% of FLC.

M1: 65 × 2.50 = 162.5A → 150A (next lower standard)

M2: 34 × 2.50 = 85A → 80A

M3: 21 × 2.50 = 52.5A → 50A

M4: 14 × 2.50 = 35A → 35A

M5: 11 × 2.50 = 27.5A → 25A

Result: Breakers: 150, 80, 50, 35, 25A

3

Size Overload Protection

NEC 430.32: SF ≥ 1.15 → overload ≤ 125% of FLA.

Using FLC as proxy for FLA (nameplate values would be used in practice):

M1: 65 × 1.25 = 81.3A

M2: 34 × 1.25 = 42.5A

M3: 21 × 1.25 = 26.3A

M4: 14 × 1.25 = 17.5A

M5: 11 × 1.25 = 13.8A

Result: Overload heaters sized per motor FLA

4

Size MCC Feeder

NEC 430.24: 125% of largest motor + 100% of all others.

125% of 65A = 81.3A.

Others: 34 + 21 + 14 + 11 = 80A.

Total feeder: 81.3 + 80 = 161.3A.

Conductor: 2/0 AWG copper (175A at 75°C) or 4/0 aluminum.

(1.25 × 65) + 34 + 21 + 14 + 11 = 161.3A

Result: 161.3A feeder → 2/0 AWG copper

5

Size Feeder SCGF

NEC 430.62: feeder SCGF = largest branch breaker + sum of other FLCs.

Largest branch breaker: 150A.

Other FLCs: 34 + 21 + 14 + 11 = 80A.

Max feeder breaker: 150 + 80 = 230A → 225A standard.

150A + (34 + 21 + 14 + 11) = 230A → 225A

Result: 225A feeder breaker

6

Verify AIC Ratings

Available fault current at MCC: 25 kAIC.

All breakers must have interrupting rating ≥ 25 kAIC.

Standard molded case breakers: typically 22 kAIC at 480V. NOT adequate.

Need high-interrupting rated breakers: 35 kAIC or 65 kAIC series.

NEC 110.9: equipment interrupting rating must exceed available fault current.

Result: All breakers must be rated ≥ 25 kAIC — select 35 kAIC series

Final Answer

MCC fed by 225A breaker, 2/0 AWG copper feeder (161.3A demand). Five motor branches: 150A/3AWG (50HP), 80A/8AWG (25HP), 50A/10AWG (15HP), 35A/14AWG (10HP), 25A/14AWG (7.5HP). All breakers rated 35 kAIC minimum for 25 kA available fault current.

Key Takeaways

  • MCC feeder uses 125% of largest motor + sum of all other FLCs (NEC 430.24)
  • Feeder SCGF = largest branch SCGF + sum of other motor FLCs (NEC 430.62)
  • Always verify AIC ratings against available fault current — standard 22 kAIC breakers are inadequate for many industrial locations
  • Overload protection uses nameplate FLA, but conductor and SCGF sizing uses NEC table FLC

Calculators Used

NEC References

  • NEC 430.22 — Motor Branch Conductor
  • NEC 430.24 — Motor Feeder
  • NEC 430.52 — Motor SCGF
  • NEC 430.62 — Feeder SCGF
  • NEC 110.9 — Interrupting Rating

Project Explorer

No Projects Found