How to Calculate Conduit Fill
- Code basis
- Chapter 9 Tables 1, 4, 5
- Method
- Area sum, not count charts
- Default limit
- 40% for 3+ conductors
- Hard case
- Mixed sizes and cables
The Procedure
5 steps, in the order the code applies them.
Step 1
List every conductor group
Group by size and insulation type. A pull with 12 AWG THHN and 10 AWG XHHW is two groups, not one average size.
Step 2
Look up each group's area
Use Chapter 9 Table 5 or 5A for the actual insulation and stranding. Compact conductors only get compact areas when they are actually compact.
Step 3
Multiply area by quantity and sum
Total conductor area is the sum of every group. Include the equipment grounding conductor — fill counts it even though derating does not.
Step 4
Select the percent fill limit
One conductor uses 53 percent, two use 31 percent, three or more use 40 percent. A nipple not over 24 inches may use 60 percent.
Step 5
Compare to raceway internal area
Read Chapter 9 Table 4 for the raceway type and trade size. If total conductor area exceeds the permitted area, enlarge the raceway or reduce the pull.
Calculate area, not count
Each conductor group contributes its own tabulated area multiplied by quantity. Mixed pulls are summed group by group.
After total area is known, compare it with the permitted area for the raceway trade size and conductor count.
When tables are not enough
Annex-style count tables are useful only for one conductor size and one insulation type. They do not answer a mixed-size pull.
Cable assemblies such as UF need manufacturer dimensions. Borrowing a similar single-conductor value can understate fill.
Decision Guide
The choices that change the answer, and how to make them.
Skip annex count tables for mixed pulls
Count charts assume one size and one insulation. They are planning shortcuts, not the answer for a mixed pull.
Cables need manufacturer dimensions
UF, MC and similar assemblies are not interchangeable with single-conductor Table 5 rows. Use the published OD or area from the maker.
Fill pass is not pull ease
A raceway can meet percent fill and still be a hard pull because of bends, length and jam ratio. Plan lubrication and pull points separately.
FAQs
How do I calculate conduit fill with different wire sizes?
Does the ground wire count in conduit fill?
When can I use 60 percent fill?
Calculated against the NEC 2023 edition using Chapter 9 Table 1, Chapter 9 Table 4, Chapter 9 Table 5. Confirm the edition adopted by your AHJ, which may differ and may carry local amendments.
Not covered by this tool
- Motor, air-conditioning and welder circuits, which are sized under their own articles.
- Conductors in free air and photovoltaic circuits.
- Parallel conductor sets, taps and busbars.
- Local amendments, which can be stricter than the published code.
Data last verified