What Size Wire for 15 Amps?
- Load
- 15 A
- Distance
- 0 ft entered
- Band
- Branch circuit
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
- Conductor count
- 3 current-carrying
Computed Starting Point
The table uses common defaults. Change the calculator inputs for the actual installation.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 14 AWG | 15 A | 15 A | Small conductor overcurrent limit | Passes defaults |
| Aluminum | 12 AWG | 15 A | 15 A | Small conductor overcurrent limit | Passes defaults |
What 15 A ChangesAt 15 A, the non-continuous default copper result is 14 AWG, protected at 15 A. The aluminum row is a calculator output for listed aluminum terminations, not the usual small branch-circuit choice; using a larger conductor does not turn the circuit into 20 A.
Adjacent Amp Ratings
Compare the next published amp rating under the same defaults.
| Load | Copper size | Copper OCPD | Aluminum size | Aluminum OCPD |
|---|---|---|---|---|
| 15 A (this page) | 14 AWG | 15 A | 12 AWG | 15 A |
| 20 A | 12 AWG | 20 A | 10 AWG | 20 A |
A plateau means neighboring amp ratings share a conductor size under these defaults. A jump means a standard breaker change often needs a larger wire; confirm with your real ambient, length and terminations.
15 A Is the Small Branch-Circuit Floor
Branch circuit context for a 15 A circuit.
A 15 A wire-size search is usually about ordinary lighting, receptacles, controls, fans, garage-door openers, or a small dedicated load. The user often wants to know whether 14 AWG copper is still the right starting point.
Under the non-continuous defaults on this page, 15 A is governed by the small-conductor overcurrent limit. There is no lower adjacent amp page here, so the useful comparison is upward: 20 A moves to a different conductor set.
What Changes This Answer
Checks that can change the starting conductor under the displayed defaults.
Do not carry 15 A logic to 20 A
The adjacent 20 A page moves to 12 AWG copper or 10 AWG aluminum under the same defaults.
Check actual load type
Lighting, receptacles and dedicated equipment can have different listing or nameplate requirements. Use the equipment instructions when they are more specific.
Watch long 120 V runs
The amp-only page assumes no distance. A long 120 V branch circuit should be checked in the calculator for voltage drop.
Rerun continuous loads
The displayed answer does not apply the 125 percent continuous-load multiplier. If the load runs three hours or more, use the calculator's continuous setting.
Treat aluminum as uncommon here
Aluminum is not typical for small branch circuits. If it is used, both the conductor size and terminations must support aluminum.