What Size Wire for 20 Amps?
- Load
- 20 A
- Distance
- 0 ft entered
- Band
- Branch circuit
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
- Conductor count
- 3 current-carrying
Computed Starting Point
The table uses common defaults. Change the calculator inputs for the actual installation.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 12 AWG | 20 A | 20 A | Small conductor overcurrent limit | Passes defaults |
| Aluminum | 10 AWG | 20 A | 25 A | Small conductor overcurrent limit | Passes defaults |
What 20 A ChangesAt 20 A, the non-continuous default copper result is 12 AWG and is capped at 20 A by the small-conductor limit. Aluminum appears as 10 AWG under the calculator defaults, but aluminum is uncommon for this branch-circuit use case.
Adjacent Amp Ratings
See whether stepping one standard size up or down forces a conductor jump under the same defaults.
| Load | Copper size | Copper OCPD | Aluminum size | Aluminum OCPD |
|---|---|---|---|---|
| 15 A | 14 AWG | 15 A | 12 AWG | 15 A |
| 20 A (this page) | 12 AWG | 20 A | 10 AWG | 20 A |
| 25 A | 10 AWG | 25 A | 10 AWG | 25 A |
A plateau means neighboring amp ratings share a conductor size under these defaults. A jump means a standard breaker change often needs a larger wire; confirm with your real ambient, length and terminations.
20 A Is the Common Branch-Circuit Step
Branch circuit context for a 20 A circuit.
A 20 A wire-size search usually comes from receptacle circuits, kitchen or laundry small-appliance circuits, garage outlets, bath loads, or a dedicated tool or equipment branch. The search intent is often practical: can this be 12 AWG copper, and what changes from 15 A?
Under the non-continuous defaults on this page, 20 A is still small-conductor governed. The important adjacent contrast is that 15 A uses 14 AWG copper, while 25 A moves copper up to 10 AWG.
What Changes This Answer
Checks that can change the starting conductor under the displayed defaults.
Keep 12 AWG on the 20 A page
Do not use the 15 A copper answer for a 20 A breaker. Under these defaults, the page moves from 14 AWG copper at 15 A to 12 AWG copper at 20 A.
Do not round 25 A down
The adjacent 25 A page changes the copper result to 10 AWG under the same defaults.
Check receptacle and equipment rules
A generic 20 A conductor answer does not replace device ratings, equipment instructions or circuit-specific rules.
Rerun continuous loads
The displayed answer does not apply the 125 percent continuous-load multiplier. A true 20 A continuous load moves beyond this amp-only default.
Use distance for long branches
The amp-only answer assumes no route length. Long 120 V or 240 V runs should be checked with the wire-size calculator.