What Size Wire for 25 Amps?
- Load
- 25 A
- Distance
- 0 ft entered
- Band
- Branch circuit
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
- Conductor count
- 3 current-carrying
Computed Starting Point
The table uses common defaults. Change the calculator inputs for the actual installation.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 10 AWG | 25 A | 30 A | Small conductor overcurrent limit | Passes defaults |
| Aluminum | 10 AWG | 25 A | 25 A | Small conductor overcurrent limit | Passes defaults |
What 25 A ChangesAt 25 A, the page sits between the common 20 A and 30 A branch-circuit answers. The computed copper size has already moved to 10 AWG; aluminum shares the same size label only under listed aluminum terminations and with less usable ampacity margin.
Adjacent Amp Ratings
See whether stepping one standard size up or down forces a conductor jump under the same defaults.
| Load | Copper size | Copper OCPD | Aluminum size | Aluminum OCPD |
|---|---|---|---|---|
| 20 A | 12 AWG | 20 A | 10 AWG | 20 A |
| 25 A (this page) | 10 AWG | 25 A | 10 AWG | 25 A |
| 30 A | 10 AWG | 30 A | 8 AWG | 30 A |
A plateau means neighboring amp ratings share a conductor size under these defaults. A jump means a standard breaker change often needs a larger wire; confirm with your real ambient, length and terminations.
25 A Is the Nameplate Middle Case
Branch circuit context for a 25 A circuit.
A 25 A wire-size search is less often a general receptacle question and more often tied to a manufacturer-specified appliance, heater, specialty receptacle, or control circuit. The right next step is usually checking the nameplate, not guessing from a nearby common breaker.
Under the non-continuous defaults, copper moves up from 12 AWG at 20 A to 10 AWG here, then stays 10 AWG at 30 A. Aluminum is already 10 AWG at 20 A and remains 10 AWG at 25 A under the displayed assumptions, but it still needs listed aluminum terminations.
What Changes This Answer
Checks that can change the starting conductor under the displayed defaults.
Start with the nameplate
Many 25 A searches come from equipment instructions. Use the manufacturer's minimum circuit ampacity and maximum overcurrent protection when provided, and do not use this page to size motor or HVAC-specific circuits.
Non-continuous default only
The displayed answer does not apply the 125 percent continuous-load multiplier. If the load runs for three hours or more, rerun the calculator with continuous load enabled.
Do not reuse 20 A copper
Under these defaults, 20 A uses 12 AWG copper but 25 A moves to 10 AWG copper.
Treat aluminum as a listed-termination case
Aluminum is not the normal small branch-circuit shortcut. Use it only where the conductor, device and equipment terminations are listed for aluminum.