What Size Wire for 175 Amps?

For 175 amps with the displayed 75 C termination defaults, start with 2/0 AWG copper or 4/0 AWG aluminum. This page is the 150-to-200 A service and large-feeder middle step, with tight 75 C margins.
Load
175 A
Distance
0 ft entered
Band
Service / large feeder
Defaults
Non-continuous, 75 C lugs, 86 F, 240 V single-phase
Conductor count
3 current-carrying

Computed Starting Point

The table uses common defaults. Change the calculator inputs for the actual installation.

MaterialComputed sizeOCPDUsable ampacityGoverning constraintDefault check
Copper2/0 AWG175 A175 ATermination rated 75 CPasses defaults
Aluminum4/0 AWG175 A180 ATermination rated 75 CPasses defaults
What Size Wire for 175 Amps? under common non-continuous defaults: THHN or XHHW-2 insulation, 75 C terminations, 86 F ambient, 240 V single-phase, no more than three current-carrying conductors, and 0 ft route length entered.

What 175 A ChangesAt 175 A, the copper row lands exactly on 175 A usable ampacity under the displayed 75 C defaults, while aluminum shows only 180 A. Equipment limited to 60 C will force larger conductors, and service conductor product rules or utility requirements can change the result.

Adjacent Amp Ratings

See whether stepping one standard size up or down forces a conductor jump under the same defaults.

LoadCopper sizeCopper OCPDAluminum sizeAluminum OCPD
150 A1/0 AWG150 A3/0 AWG150 A
175 A (this page)2/0 AWG175 A4/0 AWG175 A
200 A3/0 AWG200 A250 kcmil200 A
Copper and aluminum starting sizes for 175 A and the neighboring published amp pages, under the same defaults as the result above.

A plateau means neighboring amp ratings share a conductor size under these defaults. A jump means a standard breaker change often needs a larger wire; confirm with your real ambient, length and terminations.

175 A Is the Middle Step Before 200 A

Service / large feeder context for a 175 A circuit.

A 175 A wire-size search usually means a large feeder, service-equipment replacement, shop feed, or panel decision that sits above 150 A but is not intended to become a 200 A service by habit. The rating needs a real load or equipment reason, not just a round-number preference.

Under the displayed 75 C termination defaults, copper moves from 1/0 AWG at 150 A to 2/0 AWG here, and aluminum moves from 3/0 AWG to 4/0 AWG. The next 200 A page moves copper again to 3/0 AWG and aluminum to 250 kcmil.

What Changes This Answer

Checks that can change the starting conductor under the displayed defaults.

  • Do not reuse the 150 A answer

    Under these defaults, 150 A uses 1/0 AWG copper and 3/0 AWG aluminum. This 175 A page moves to 2/0 AWG copper and 4/0 AWG aluminum.

  • Watch the exact copper margin

    The displayed copper row has no extra ampacity above 175 A under 75 C defaults. Derating, long runs, or product limits can move the final size.

  • Check 60 C equipment limits

    The 2/0 AWG copper and 4/0 AWG aluminum results are 75 C defaults. Equipment limited to 60 C will force larger conductors for a full 175 A feeder or service.

  • Compare 200 A before standardizing

    The adjacent 200 A page moves copper to 3/0 AWG and aluminum to 250 kcmil under the same defaults. Do not drift to 200 A without load and equipment support.

  • Confirm service product and utility rules

    Service-entrance cable, raceway conductors, meter lugs, disconnect lugs, utility standards, and AHJ review can all override a generic starting point.

175 Amp Wire Size FAQs

What size wire for 175 amps?
Under the 75 C non-continuous defaults on this page, start with 2/0 AWG copper or 4/0 AWG aluminum. Treat this as a planning starting point only, then confirm the conductor product, terminal rating, load calculation, route length, and utility or AHJ requirements.
Is 175 A the same wire size as 150 A?
No under these defaults. The 150 A page shows 1/0 AWG copper and 3/0 AWG aluminum, while 175 A moves to 2/0 AWG copper and 4/0 AWG aluminum.
Should I use the 200 A page instead?
Only when the load calculation, service equipment, overcurrent device, and utility or AHJ requirements support a 200 A rating. The 200 A page uses larger conductors under these defaults.
Can 2/0 copper be used for every 175 A feeder?
No. It is the displayed 75 C default starting point. Equipment limited to 60 C, derating, voltage drop, or a different conductor product can force a larger conductor.