What Size Wire for 400 Amps?
- Load
- 400 A
- Distance
- 0 ft entered
- Band
- Large service / feeder
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
- Conductor count
- 3 current-carrying
Computed Starting Point
The table uses common defaults. Change the calculator inputs for the actual installation.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 600 kcmil | 400 A | 420 A | Termination rated 75 C | Passes defaults |
| Aluminum | 900 kcmil | 400 A | 425 A | Termination rated 75 C | Passes defaults |
What 400 A ChangesAt 400 A, copper shows 420 A usable ampacity and aluminum shows 425 A under the displayed 75 C defaults. That passes the default check, but equipment limited to 60 C falls below a full 400 A rating, and many real 400 A installations depend on listed service assemblies, utility requirements, raceway strategy, or engineered parallel sets.
Adjacent Amp Ratings
Compare the prior published amp rating; this is the highest amp-only answer page in the published set.
| Load | Copper size | Copper OCPD | Aluminum size | Aluminum OCPD |
|---|---|---|---|---|
| 350 A | 500 kcmil | 350 A | 700 kcmil | 350 A |
| 400 A (this page) | 600 kcmil | 400 A | 900 kcmil | 400 A |
This ceiling comparison shows what changes from the prior published amp rating. For ratings above 400 A, use the calculator with real inputs instead of extrapolating from this page.
400 A Is the Published Amp-Series Ceiling
Large service / feeder context for a 400 A circuit.
A 400 A wire-size search usually means a large residential service, meter-main lineup, building feeder, shop service, or light commercial distribution path. At this rating, the conductor number is only one part of the decision; equipment lineup, utility standards, service product, raceway layout, and installation method can control the accepted design.
Under the displayed 75 C termination defaults, copper moves from 500 kcmil at 350 A to 600 kcmil here, and aluminum moves from 700 kcmil to 900 kcmil. There is no higher published amp-only answer page in this series, so designs above 400 A should go back to the calculator and a project-specific review instead of extrapolating from this page.
What Changes This Answer
Checks that can change the starting conductor under the displayed defaults.
Do not reuse 350 A conductors
Under these defaults, 350 A uses 500 kcmil copper and 700 kcmil aluminum. This 400 A page moves to 600 kcmil copper and 900 kcmil aluminum.
Treat this as the page-series ceiling
The amp-only answer set stops at 400 A. For larger ratings, use the calculator with real inputs and a project-specific design review rather than extending the adjacent table by guesswork.
Check 60 C and equipment listings
The displayed 600 kcmil copper and 900 kcmil aluminum results are 75 C defaults. Equipment limited to 60 C will force a different conductor or assembly for a full 400 A feeder or service.
Verify service gear and utility standards
Meter-main equipment, service disconnects, CT cabinets, utility standards, grounding, bonding, and AHJ review can require an accepted assembly that differs from a single-conductor table starting point.
Do not size parallel sets from this page
Parallel conductors are common at this scale, but this page does not design them. Parallel sets need matching conductors, equal lengths, listed terminations, and project-specific engineering.