What Size Wire for 50 Amps at 100 Feet?
- Load
- 50 A
- Distance
- 100 ft
- Band
- Mid branch / light feeder
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
Computed Starting Point
Ampacity and voltage drop under common defaults for this amp and distance.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 6 AWG | 50 A | 65 A | Voltage drop | Passes defaults |
| Aluminum | 4 AWG | 50 A | 65 A | Voltage drop | Passes defaults |
What 100 ft ChangesAt 100 ft, the result moves from 8 AWG copper and 6 AWG aluminum at zero length to 6 AWG copper and 4 AWG aluminum. The breaker is still 50 A; the larger conductor is buying voltage-drop margin under the stated defaults.
Zero-Length vs This Distance
If the distance-adjusted size is larger, voltage drop governed under these defaults.
| Case | Copper size | Copper constraint | Aluminum size | Aluminum constraint |
|---|---|---|---|---|
| Ampacity only (0 ft) | 8 AWG | Termination rated 75 C | 6 AWG | Termination rated 75 C |
| 100 ft (this page) | 6 AWG | Voltage drop | 4 AWG | Voltage drop |
Adjacent Distances at This Amp
Neighboring published lengths for 50 A under the same defaults.
| Distance | Copper size | Aluminum size | Copper constraint |
|---|---|---|---|
| 100 ft (this page) | 6 AWG | 4 AWG | Voltage drop |
| 150 ft | 4 AWG | 3 AWG | Voltage drop |
100 ft Is the First 50 A Distance Page
Mid branch / light feeder context for 50 A at 100 ft.
A 50 A run at 100 ft is often an EVSE branch circuit, small shop feeder, detached-garage feed, welder outlet, or longer equipment circuit. The common mistake is to start from the short-circuit conductor and ignore the measured path.
Under the defaults on this page, both materials are already larger than the zero-length ampacity result. That makes 100 ft the first 50 A page where the user should treat distance as part of the conductor choice.
What Changes This Long-Run Answer
Checks that matter for distance-governed sizing in this amp band.
Measure the one-way path
Count the route through walls, trench, risers and equipment offsets. A guessed 100 ft run can land closer to the 150 ft page.
Do not raise the breaker
The distance-driven upsize does not authorize more than the intended 50 A overcurrent device, and grounding conductor sizing should be checked after a drop-driven conductor increase.
Confirm 240 V assumptions
These defaults assume 240 V single-phase. A 120 V load at the same current and distance needs its own calculator run.
Check aluminum terminations
4 AWG aluminum can be attractive on cost, but only if the equipment lugs and installation method accept the material and size.