What Size Wire for 50 Amps at 150 Feet?
- Load
- 50 A
- Distance
- 150 ft
- Band
- Mid branch / light feeder
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
Computed Starting Point
Ampacity and voltage drop under common defaults for this amp and distance.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 4 AWG | 50 A | 85 A | Voltage drop | Passes defaults |
| Aluminum | 3 AWG | 50 A | 75 A | Voltage drop | Passes defaults |
What 150 ft ChangesAt 150 ft, both materials are voltage-drop governed, but the neighboring pages do not move together. This page is the midpoint where copper has made its next jump while aluminum still has another published jump ahead at 200 ft.
Zero-Length vs This Distance
If the distance-adjusted size is larger, voltage drop governed under these defaults.
| Case | Copper size | Copper constraint | Aluminum size | Aluminum constraint |
|---|---|---|---|---|
| Ampacity only (0 ft) | 8 AWG | Termination rated 75 C | 6 AWG | Termination rated 75 C |
| 150 ft (this page) | 4 AWG | Voltage drop | 3 AWG | Voltage drop |
Adjacent Distances at This Amp
Neighboring published lengths for 50 A under the same defaults.
| Distance | Copper size | Aluminum size | Copper constraint |
|---|---|---|---|
| 100 ft | 6 AWG | 4 AWG | Voltage drop |
| 150 ft (this page) | 4 AWG | 3 AWG | Voltage drop |
| 200 ft | 4 AWG | 2 AWG | Voltage drop |
150 ft Is the 50 A Middle Transition
Mid branch / light feeder context for 50 A at 150 ft.
A 150 ft 50 A run is the kind of measured path that shows up after adding risers, sweeps, garage offsets, EVSE placement, or a small shop feeder route. It is not just a rounded-up 100 ft query.
Under the defaults, copper jumps from 6 AWG at 100 ft to 4 AWG here, then stays 4 AWG at 200 ft. Aluminum steps differently: 4 AWG at 100 ft, 3 AWG here, and 2 AWG at 200 ft.
What Changes This Long-Run Answer
Checks that matter for distance-governed sizing in this amp band.
Compare all three 50 A pages
100 ft, 150 ft and 200 ft do not share the same material pattern. Use the measured route before choosing a conductor.
Use actual operating current
A configured EVSE or equipment load below 50 A can change the voltage-drop result. Do not size from the breaker handle when the sustained load is lower.
Keep 120 V separate
These defaults assume 240 V. The same 50 A at 120 V has a different voltage-drop problem and should be rerun.
Check terminations after upsizing
The larger conductor is only useful if the receptacle, disconnect, panel or feeder equipment accepts the chosen material and size.