What Size Wire for 50 Amps at 200 Feet?
- Load
- 50 A
- Distance
- 200 ft
- Band
- Mid branch / light feeder
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
Computed Starting Point
Ampacity and voltage drop under common defaults for this amp and distance.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 4 AWG | 50 A | 85 A | Voltage drop | Passes defaults |
| Aluminum | 2 AWG | 50 A | 90 A | Voltage drop | Passes defaults |
What 200 ft ChangesAt 200 ft, the page sits at the top of the published 50 A distance series. The copper result matches 150 ft, but aluminum moves again, so material choice affects both cost and installability more than a generic 50 A chart suggests.
Zero-Length vs This Distance
If the distance-adjusted size is larger, voltage drop governed under these defaults.
| Case | Copper size | Copper constraint | Aluminum size | Aluminum constraint |
|---|---|---|---|---|
| Ampacity only (0 ft) | 8 AWG | Termination rated 75 C | 6 AWG | Termination rated 75 C |
| 200 ft (this page) | 4 AWG | Voltage drop | 2 AWG | Voltage drop |
Adjacent Distances at This Amp
Neighboring published lengths for 50 A under the same defaults.
| Distance | Copper size | Aluminum size | Copper constraint |
|---|---|---|---|
| 150 ft | 4 AWG | 3 AWG | Voltage drop |
| 200 ft (this page) | 4 AWG | 2 AWG | Voltage drop |
200 ft Is the Last 50 A Published Distance
Mid branch / light feeder context for 50 A at 200 ft.
A 200 ft 50 A run is usually a long EVSE branch, detached-garage circuit, small shop feeder, pump, welder or equipment run where the exact one-way conductor path needs to be final before buying wire.
This page is not the first voltage-drop warning; 100 ft already upsized under the defaults. Its distinct point is that copper remains 4 AWG from 150 ft, while aluminum takes another step to 2 AWG.
What Changes This Long-Run Answer
Checks that matter for distance-governed sizing in this amp band.
Do not extrapolate past 200 ft
This is the last published 50 A distance answer. If the route is longer, rerun the calculator with the measured one-way path.
Compare copper plateau and aluminum jump
Copper holds at 4 AWG from 150 ft to 200 ft under these defaults, while aluminum changes from 3 AWG to 2 AWG.
Recheck configured load
Many 50 A circuits do not operate at 50 A continuously. Use the actual expected current when voltage drop is the design concern.
Confirm larger aluminum fit
2 AWG aluminum affects lug range, raceway fill and bend space. Verify the physical installation before choosing material by price alone.