What Size Wire for 60 Amps at 100 Feet?
- Load
- 60 A
- Distance
- 100 ft
- Band
- Mid branch / light feeder
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
Computed Starting Point
Ampacity and voltage drop under common defaults for this amp and distance.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 6 AWG | 60 A | 65 A | Termination rated 75 C | Passes defaults |
| Aluminum | 4 AWG | 60 A | 65 A | Termination rated 75 C | Passes defaults |
What 100 ft ChangesAt 100 ft, the displayed 60 A result remains 6 AWG copper or 4 AWG aluminum and stays termination-governed under the page defaults. The useful distinction is that the next published distance, 150 ft, moves both materials larger for voltage drop.
Zero-Length vs This Distance
If the distance-adjusted size is larger, voltage drop governed under these defaults.
| Case | Copper size | Copper constraint | Aluminum size | Aluminum constraint |
|---|---|---|---|---|
| Ampacity only (0 ft) | 6 AWG | Termination rated 75 C | 4 AWG | Termination rated 75 C |
| 100 ft (this page) | 6 AWG | Termination rated 75 C | 4 AWG | Termination rated 75 C |
Adjacent Distances at This Amp
Neighboring published lengths for 60 A under the same defaults.
| Distance | Copper size | Aluminum size | Copper constraint |
|---|---|---|---|
| 100 ft (this page) | 6 AWG | 4 AWG | Termination rated 75 C |
| 150 ft | 4 AWG | 2 AWG | Voltage drop |
100 ft Is the 60 A Short-Run Platform
Mid branch / light feeder context for 60 A at 100 ft.
A 60 A run at 100 ft is often a garage EVSE circuit, spa, small equipment feed, pump, welder outlet, or light feeder where the user wants to know whether distance changes the usual 60 A conductor.
Under the defaults on this page, 100 ft does not move the result above the zero-length conductor. That makes this page a boundary check before the published 150 ft page, where voltage drop starts changing the 60 A answer.
What Changes This Long-Run Answer
Checks that matter for distance-governed sizing in this amp band.
Do not assume 100 ft has jumped
The zero-length and 100 ft rows match under these defaults. If your measured route is closer to 150 ft, use the next distance page or the calculator.
Use the real one-way route
Panel location, wall offsets, trench detours, risers and sweeps all count toward the distance input.
Keep 240 V and load assumptions visible
These defaults assume 240 V single-phase and a 60 A load. A 120 V circuit or different operating current needs a separate run.
Check lugs before buying aluminum
4 AWG aluminum is only useful if the equipment accepts aluminum conductors at the listed temperature and size.