What Size Wire for 60 Amps at 150 Feet?
- Load
- 60 A
- Distance
- 150 ft
- Band
- Mid branch / light feeder
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
Computed Starting Point
Ampacity and voltage drop under common defaults for this amp and distance.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 4 AWG | 60 A | 85 A | Voltage drop | Passes defaults |
| Aluminum | 2 AWG | 60 A | 90 A | Voltage drop | Passes defaults |
What 150 ft ChangesAt 150 ft, the 60 A series crosses from termination-governed sizing into voltage-drop-governed sizing under the page defaults. The result moves from 6 AWG copper and 4 AWG aluminum at 100 ft to 4 AWG copper and 2 AWG aluminum here.
Zero-Length vs This Distance
If the distance-adjusted size is larger, voltage drop governed under these defaults.
| Case | Copper size | Copper constraint | Aluminum size | Aluminum constraint |
|---|---|---|---|---|
| Ampacity only (0 ft) | 6 AWG | Termination rated 75 C | 4 AWG | Termination rated 75 C |
| 150 ft (this page) | 4 AWG | Voltage drop | 2 AWG | Voltage drop |
Adjacent Distances at This Amp
Neighboring published lengths for 60 A under the same defaults.
| Distance | Copper size | Aluminum size | Copper constraint |
|---|---|---|---|
| 100 ft | 6 AWG | 4 AWG | Termination rated 75 C |
| 150 ft (this page) | 4 AWG | 2 AWG | Voltage drop |
| 200 ft | 3 AWG | 1 AWG | Voltage drop |
150 ft Is the First 60 A Upsize
Mid branch / light feeder context for 60 A at 150 ft.
A 150 ft 60 A route often appears after adding garage offsets, EVSE placement, spa location, equipment-pad routing, trench bends or a small shop feeder path. It is the point where the measured route can no longer borrow the 100 ft result.
Under the defaults, 100 ft still matches the short-run platform. At 150 ft, both copper and aluminum move larger for voltage drop, and the 200 ft page moves again.
What Changes This Long-Run Answer
Checks that matter for distance-governed sizing in this amp band.
Do not reuse the 100 ft result
Under these defaults, 100 ft and 150 ft are different 60 A answers. Measure before ordering conductor.
Check 200 ft if the route can grow
The 200 ft page is not a plateau. It moves again to 3 AWG copper and 1 AWG aluminum under the same assumptions.
Use actual operating current
Voltage drop follows the current that flows. A configured EVSE or equipment load below the breaker handle can change the result.
Keep 120 V separate
The displayed page defaults are 240 V single-phase. A 120 V circuit at 150 ft should be run in the calculator.