What Size Wire for 60 Amps at 200 Feet?
- Load
- 60 A
- Distance
- 200 ft
- Band
- Mid branch / light feeder
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
Computed Starting Point
Ampacity and voltage drop under common defaults for this amp and distance.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 3 AWG | 60 A | 100 A | Voltage drop | Passes defaults |
| Aluminum | 1 AWG | 60 A | 100 A | Voltage drop | Passes defaults |
What 200 ft ChangesAt 200 ft, the result moves from 4 AWG copper and 2 AWG aluminum at 150 ft to 3 AWG copper and 1 AWG aluminum. Both materials step again, so this page is a final measured-route check rather than a generic 60 A chart.
Zero-Length vs This Distance
If the distance-adjusted size is larger, voltage drop governed under these defaults.
| Case | Copper size | Copper constraint | Aluminum size | Aluminum constraint |
|---|---|---|---|---|
| Ampacity only (0 ft) | 6 AWG | Termination rated 75 C | 4 AWG | Termination rated 75 C |
| 200 ft (this page) | 3 AWG | Voltage drop | 1 AWG | Voltage drop |
Adjacent Distances at This Amp
Neighboring published lengths for 60 A under the same defaults.
| Distance | Copper size | Aluminum size | Copper constraint |
|---|---|---|---|
| 150 ft | 4 AWG | 2 AWG | Voltage drop |
| 200 ft (this page) | 3 AWG | 1 AWG | Voltage drop |
200 ft Is the Second 60 A Jump
Mid branch / light feeder context for 60 A at 200 ft.
A 200 ft 60 A run is a long EVSE branch, detached garage or shop feeder, spa, pump, welder or equipment route where the exact one-way path should be final before buying conductor.
This page is not the first 60 A voltage-drop upsize. The 150 ft page already moved larger, and 200 ft moves both materials again under the same defaults.
What Changes This Long-Run Answer
Checks that matter for distance-governed sizing in this amp band.
Do not borrow the 150 ft result
Under these defaults, both materials change between 150 ft and 200 ft. Use the page matching the measured route.
Rerun anything longer
This is the last published 60 A distance answer. Longer one-way paths should be checked in the calculator rather than extrapolated.
Confirm load and voltage
A different operating current, 120 V load, continuous-load treatment or three-phase system can change the conductor result.
Check larger conductor fit
3 AWG copper and 1 AWG aluminum affect lug range, raceway fill and bend space. Verify the physical installation before ordering.