What Size Breaker for 4 AWG Wire?
- Wire
- 4 AWG
- Band
- Mid branch / appliance
- Scope
- Branch / feeder check
- Next
- Compatibility calculator
Breaker Starting Point
Maximum common breaker sizes under common conditions. Derating or receptacle limits can reduce these.
| Material | Conductor | Largest common breaker | Assumptions |
|---|---|---|---|
| Copper | 4 AWG copper | 90 A | 90 C insulation, 75 C lugs, 86 F, 3 current-carrying conductors, non-receptacle circuit default |
| Aluminum | 4 AWG aluminum | 70 A | 90 C insulation, 75 C lugs, 86 F, 3 current-carrying conductors, non-receptacle circuit default |
What 4 AWG ChangesAt 4 AWG, the page is a feeder-planning boundary. The displayed 90 A copper and 70 A aluminum maximums depend on the non-receptacle next-size-up default, and the next published 3 AWG page moves into the large-feeder band.
Adjacent Wire Sizes
See whether stepping one conductor size changes the maximum standard breaker.
| Wire | Copper max breaker | Aluminum max breaker |
|---|---|---|
| 6 AWG | 70 A | 50 A |
| 4 AWG (this page) | 90 A | 70 A |
| 3 AWG | 100 A | 80 A |
4 AWG Is the Last Mid-Branch Step
Mid branch / appliance context for 4 AWG wire.
A 4 AWG breaker-size search often points to a larger equipment feeder, subpanel, shop circuit, or a planned step above common 60 A work. At this size, voltage drop, lug range, and load calculation are no longer side notes.
Under the displayed defaults, 4 AWG copper reaches a 90 A maximum breaker and 4 AWG aluminum reaches 70 A. Both results lean on the non-receptacle next-size-up path because the 75 C ampacity values sit between standard breaker ratings.
Field Checks for This Wire Size
Checks that matter in this conductor band — not a generic breaker list.
Do not reuse 6 AWG answers
Under these defaults, 6 AWG copper returns 70 A and 6 AWG aluminum returns 50 A. This 4 AWG page moves both materials larger.
Check next-size-up eligibility
The displayed 90 A copper and 70 A aluminum maximums depend on the non-receptacle next-size-up default. Confirm the circuit type before rounding above usable ampacity.
Plan lugs and raceway
Subpanels, disconnects, and equipment lugs must accept 4 AWG in the chosen material. Raceway fill and bending space can also drive the final design.
Run load and voltage-drop checks
A breaker maximum only protects the conductor. Long feeders and calculated loads can require a larger conductor even when the breaker compatibility table passes.