What Size Wire for 200 Amps at 100 Feet?
- Load
- 200 A
- Distance
- 100 ft
- Band
- 200 A feeder / service
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
Computed Starting Point
Ampacity and voltage drop under common defaults for this amp and distance.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 3/0 AWG | 200 A | 200 A | Termination rated 75 C | Passes defaults |
| Aluminum | 250 kcmil | 200 A | 205 A | Termination rated 75 C | Passes defaults |
What 100 ft ChangesAt 100 ft, voltage drop is visible but not the governing constraint under the default 200 A setup. The practical work is confirming conductor product, lug temperature, meter/panel acceptance and whether the AHJ or utility treats this as service equipment rather than a generic feeder.
Zero-Length vs This Distance
If the distance-adjusted size is larger, voltage drop governed under these defaults.
| Case | Copper size | Copper constraint | Aluminum size | Aluminum constraint |
|---|---|---|---|---|
| Ampacity only (0 ft) | 3/0 AWG | Termination rated 75 C | 250 kcmil | Termination rated 75 C |
| 100 ft (this page) | 3/0 AWG | Termination rated 75 C | 250 kcmil | Termination rated 75 C |
Adjacent Distances at This Amp
Neighboring published lengths for 200 A under the same defaults.
| Distance | Copper size | Aluminum size | Copper constraint |
|---|---|---|---|
| 100 ft (this page) | 3/0 AWG | 250 kcmil | Termination rated 75 C |
| 150 ft | 3/0 AWG | 250 kcmil | Termination rated 75 C |
100 ft Is the Short 200 A Platform
200 A feeder / service context for 200 A at 100 ft.
A 200 A run at 100 ft is often a service upgrade, meter-to-panel relocation, short detached-building feeder, or large residential subfeed. The user usually knows the 200 A rating and is checking whether distance changes the conductor.
Under the defaults on this page, 100 ft does not move the result above the zero-length conductor. That makes this page a service/feeder product and termination check, not a voltage-drop jump page.
What Changes This Long-Run Answer
Checks that matter for distance-governed sizing in this amp band.
Separate service from feeder
A 200 A service lateral, service-entrance conductor and feeder can follow different product and approval paths. Do not use this as a utility standard by itself.
Confirm lugs before conductor
The 3/0 copper or 250 kcmil aluminum result is only useful if the meter, panel or disconnect accepts that material and temperature rating.
Use 100 ft as the platform check
Because the zero-length and 100 ft rows match under these defaults, this page tells you distance has not yet beaten the product/termination floor.
Watch the 250 ft break
The published 150 ft and 200 ft pages stay on the same platform, but the 250 ft page jumps for voltage drop under the same assumptions.