What Size Wire for 200 Amps at 400 Feet?

At 400 ft, the default 200 A answer reaches the largest published distance page: 300 kcmil copper or 500 kcmil aluminum, with voltage drop driving the result.
Load
200 A
Distance
400 ft
Band
200 A feeder / service
Defaults
Non-continuous, 75 C lugs, 86 F, 240 V single-phase

Computed Starting Point

Ampacity and voltage drop under common defaults for this amp and distance.

MaterialComputed sizeOCPDUsable ampacityGoverning constraintDefault check
Copper300 kcmil200 A285 AVoltage dropPasses defaults
Aluminum500 kcmil200 A310 AVoltage dropPasses defaults
What Size Wire for 200 Amps at 400 Feet? under common non-continuous defaults: THHN or XHHW-2 insulation, 75 C terminations, 86 F ambient, 240 V single-phase and no more than three current-carrying conductors.

What 400 ft ChangesAt 400 ft, the page is the end of the published 200 A distance series. The default result moves from 250 kcmil copper and 400 kcmil aluminum at 300 ft to 300 kcmil copper and 500 kcmil aluminum here, so route and load assumptions deserve a fresh check.

Zero-Length vs This Distance

If the distance-adjusted size is larger, voltage drop governed under these defaults.

CaseCopper sizeCopper constraintAluminum sizeAluminum constraint
Ampacity only (0 ft)3/0 AWGTermination rated 75 C250 kcmilTermination rated 75 C
400 ft (this page)300 kcmilVoltage drop500 kcmilVoltage drop
Copper and aluminum sizes for 200 A with no distance entered versus 400 ft one-way.

Adjacent Distances at This Amp

Neighboring published lengths for 200 A under the same defaults.

DistanceCopper sizeAluminum sizeCopper constraint
300 ft250 kcmil400 kcmilVoltage drop
400 ft (this page)300 kcmil500 kcmilVoltage drop
200 A copper and aluminum starting sizes across neighboring distance pages.

400 ft Is the Extreme 200 A Route

200 A feeder / service context for 200 A at 400 ft.

A 400 ft 200 A run is no longer a casual distance adjustment. It usually points to a remote shop, barn, equipment pad, detached building or long service-planning route where the site layout and electrical assumptions should be reviewed together.

Under the defaults on this page, the answer is another large step above 300 ft. The practical question is whether the full 200 A load really needs to travel the entire measured route, and whether the selected conductor can be installed cleanly.

What Changes This Long-Run Answer

Checks that matter for distance-governed sizing in this amp band.

  • Do not extend beyond 400 ft by guesswork

    This is the last published 200 A distance page. If the measured path is longer, rerun the calculator with the real distance instead of extrapolating.

  • Recheck whether 200 A is the load

    A service or panel rating is not always the operating current used for voltage drop. A lower calculated load can materially change long-run sizing.

  • Verify large-conductor constructability

    300 kcmil copper and 500 kcmil aluminum affect conduit size, bends, pulling setup and terminations. Confirm the installation path before ordering.

  • Review equipment placement

    At this distance, moving equipment, shortening the feeder, or splitting loads can be part of the planning conversation before accepting a very large conductor run.

200 A at 400 ft FAQs

What size wire for 200 amps at 400 feet?
Under the defaults on this page, start with 300 kcmil copper or 500 kcmil aluminum. Voltage drop drives the distance-adjusted result.
Why is 400 ft larger than 300 ft?
The 300 ft page lands on 250 kcmil copper or 400 kcmil aluminum. At 400 ft, the default voltage-drop check moves both materials to the next larger published sizes.
Can I use the 300 ft result for a 400 ft route?
Not under these defaults. A measured 400 ft one-way conductor path lands on 300 kcmil copper or 500 kcmil aluminum here.
Is 400 ft one-way or round-trip distance?
Use the one-way conductor path in the calculator and on this answer page. The voltage-drop math accounts for the circuit path internally.