What Size Wire for 200 Amps at 300 Feet?
- Load
- 200 A
- Distance
- 300 ft
- Band
- 200 A feeder / service
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
Computed Starting Point
Ampacity and voltage drop under common defaults for this amp and distance.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 250 kcmil | 200 A | 255 A | Voltage drop | Passes defaults |
| Aluminum | 400 kcmil | 200 A | 270 A | Voltage drop | Passes defaults |
What 300 ft ChangesAt 300 ft, both materials are past the short-run platform and the first 250 ft jump. The page is a route-certainty and equipment-planning checkpoint between the 250 ft result below it and the 400 ft result above it.
Zero-Length vs This Distance
If the distance-adjusted size is larger, voltage drop governed under these defaults.
| Case | Copper size | Copper constraint | Aluminum size | Aluminum constraint |
|---|---|---|---|---|
| Ampacity only (0 ft) | 3/0 AWG | Termination rated 75 C | 250 kcmil | Termination rated 75 C |
| 300 ft (this page) | 250 kcmil | Voltage drop | 400 kcmil | Voltage drop |
Adjacent Distances at This Amp
Neighboring published lengths for 200 A under the same defaults.
| Distance | Copper size | Aluminum size | Copper constraint |
|---|---|---|---|
| 250 ft | 4/0 AWG | 300 kcmil | Voltage drop |
| 300 ft (this page) | 250 kcmil | 400 kcmil | Voltage drop |
| 400 ft | 300 kcmil | 500 kcmil | Voltage drop |
300 ft Is the Middle Long-Run Jump
200 A feeder / service context for 200 A at 300 ft.
A 300 ft 200 A search usually means a detached shop, barn, equipment pad, remote panel or long driveway route where the conductor path is already a design decision. Small layout changes can move the project into a different neighboring page.
This is not the first 200 A voltage-drop jump; 250 ft already moved up. At 300 ft, copper leaves AWG sizing for 250 kcmil, and aluminum moves to 400 kcmil under the same defaults.
What Changes This Long-Run Answer
Checks that matter for distance-governed sizing in this amp band.
Choose between 250, 300 and 400 ft
Use the measured one-way path rather than a rounded site distance. The neighboring 200 A pages show different conductor landings at each step.
Rerun for load below 200 A
If the actual sustained load is below the panel or service rating, voltage drop may not require the same conductor size.
Keep input defaults visible
A 120 V load, three-phase system, hotter ambient, continuous load or extra current-carrying conductors should be checked in the calculator instead of borrowed from this page.
Confirm physical fit
250 kcmil copper and 400 kcmil aluminum affect raceway, pull planning, bend space and terminations. Treat those as part of the sizing decision.