What Size Wire for 200 Amps at 250 Feet?

At 250 ft, the default 200 A answer makes its first distance-driven jump: 4/0 AWG copper or 300 kcmil aluminum, with voltage drop now governing under the page assumptions.
Load
200 A
Distance
250 ft
Band
200 A feeder / service
Defaults
Non-continuous, 75 C lugs, 86 F, 240 V single-phase

Computed Starting Point

Ampacity and voltage drop under common defaults for this amp and distance.

MaterialComputed sizeOCPDUsable ampacityGoverning constraintDefault check
Copper4/0 AWG200 A230 AVoltage dropPasses defaults
Aluminum300 kcmil200 A230 AVoltage dropPasses defaults
What Size Wire for 200 Amps at 250 Feet? under common non-continuous defaults: THHN or XHHW-2 insulation, 75 C terminations, 86 F ambient, 240 V single-phase and no more than three current-carrying conductors.

What 250 ft ChangesAt 250 ft, voltage drop becomes the governing constraint for both materials under the default 200 A setup. The result moves from 3/0 copper and 250 kcmil aluminum at 200 ft to 4/0 copper and 300 kcmil aluminum here, while 300 ft moves again.

Zero-Length vs This Distance

If the distance-adjusted size is larger, voltage drop governed under these defaults.

CaseCopper sizeCopper constraintAluminum sizeAluminum constraint
Ampacity only (0 ft)3/0 AWGTermination rated 75 C250 kcmilTermination rated 75 C
250 ft (this page)4/0 AWGVoltage drop300 kcmilVoltage drop
Copper and aluminum sizes for 200 A with no distance entered versus 250 ft one-way.

Adjacent Distances at This Amp

Neighboring published lengths for 200 A under the same defaults.

DistanceCopper sizeAluminum sizeCopper constraint
200 ft3/0 AWG250 kcmilTermination rated 75 C
250 ft (this page)4/0 AWG300 kcmilVoltage drop
300 ft250 kcmil400 kcmilVoltage drop
200 A copper and aluminum starting sizes across neighboring distance pages.

250 ft Is the First 200 A Upsize

200 A feeder / service context for 200 A at 250 ft.

A 250 ft 200 A route is often the point where a detached shop, ADU, barn, remote panel or service-equipment relocation stops behaving like a short feeder. The measured one-way conductor path matters more than the straight-line distance on a site plan.

Under the defaults on this page, 200 ft still sits on the short-run platform, but 250 ft moves up to larger conductors. This page should help the user notice that transition before buying from the shorter-distance answer.

What Changes This Long-Run Answer

Checks that matter for distance-governed sizing in this amp band.

  • Measure before choosing 200 or 250 ft

    Include trench offsets, risers, sweeps and panel placement in the one-way conductor path. If the route is really near 250 ft, do not buy from the 200 ft result.

  • Check actual current

    Voltage drop follows the current that flows. If 200 A is a panel or service rating rather than the expected load, rerun the calculator with the project current.

  • Plan for larger conductors

    4/0 copper and 300 kcmil aluminum need compatible product choices, lugs, bend space and raceway planning before the material decision is useful.

  • Compare 250 and 300 ft early

    The 300 ft page steps up again under the same defaults. If the final route may be 260 ft or longer, check the next page before locking the layout.

200 A at 250 ft FAQs

What size wire for 200 amps at 250 feet?
Under the defaults on this page, start with 4/0 AWG copper or 300 kcmil aluminum. Voltage drop governs the distance-adjusted result.
Why is 250 ft different from 200 ft?
The 200 ft page still lands on 3/0 copper or 250 kcmil aluminum under these defaults. At 250 ft, the voltage-drop check pushes both materials to the next larger published size.
Can I use the 200 ft result for a 250 ft route?
Not under these defaults. Use the measured one-way conductor length; if it is near 250 ft, this page or the calculator is the safer planning reference.
What if my 250 ft route may become 275 ft?
Compare the 300 ft page or rerun the calculator with the final measured path. The next published 200 A distance page moves to larger conductors.