What Size Wire for 200 Amps at 200 Feet?
- Load
- 200 A
- Distance
- 200 ft
- Band
- 200 A feeder / service
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
Computed Starting Point
Ampacity and voltage drop under common defaults for this amp and distance.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 3/0 AWG | 200 A | 200 A | Termination rated 75 C | Passes defaults |
| Aluminum | 250 kcmil | 200 A | 205 A | Termination rated 75 C | Passes defaults |
What 200 ft ChangesAt 200 ft, the page is a boundary result. It still returns 3/0 copper or 250 kcmil aluminum under the stated defaults, but the next 50 ft changes the sizing. Treat this as a final route-confirmation page before buying from the shorter-run platform.
Zero-Length vs This Distance
If the distance-adjusted size is larger, voltage drop governed under these defaults.
| Case | Copper size | Copper constraint | Aluminum size | Aluminum constraint |
|---|---|---|---|---|
| Ampacity only (0 ft) | 3/0 AWG | Termination rated 75 C | 250 kcmil | Termination rated 75 C |
| 200 ft (this page) | 3/0 AWG | Termination rated 75 C | 250 kcmil | Termination rated 75 C |
Adjacent Distances at This Amp
Neighboring published lengths for 200 A under the same defaults.
| Distance | Copper size | Aluminum size | Copper constraint |
|---|---|---|---|
| 150 ft | 3/0 AWG | 250 kcmil | Termination rated 75 C |
| 200 ft (this page) | 3/0 AWG | 250 kcmil | Termination rated 75 C |
| 250 ft | 4/0 AWG | 300 kcmil | Voltage drop |
200 ft Is the Last Short-Platform Page
200 A feeder / service context for 200 A at 200 ft.
A 200 ft 200 A route is a serious feeder or service-planning distance: detached shop, large ADU, remote panel, or long service-equipment relocation. Material choice and utility/AHJ approval are now part of the decision.
Under the defaults on this page, the conductor result still matches 100 ft and 150 ft. The important distinction is that 200 ft is the last published stop before the 250 ft page moves to larger conductors for voltage drop.
What Changes This Long-Run Answer
Checks that matter for distance-governed sizing in this amp band.
Do not guess between 200 and 250 ft
If the measured path is uncertain, compare both pages. Under these defaults, 200 ft holds the platform while 250 ft jumps to larger conductors.
Confirm raceway and termination together
Even without a drop upsize, 3/0 copper and 250 kcmil aluminum need equipment lugs, bend space and raceway planning that match the installed product.
Recheck actual load current
Voltage drop follows current. If 200 A is a panel rating rather than the sustained design load, rerun the calculator with the expected load.
Keep utility/AHJ constraints visible
A 200 A service-related run can be constrained by the utility, meter equipment and local practice beyond this planning result.