What Size Wire for 40 Amps?
- Load
- 40 A
- Distance
- 0 ft entered
- Band
- Appliance / mid branch
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
- Conductor count
- 3 current-carrying
Computed Starting Point
The table uses common defaults. Change the calculator inputs for the actual installation.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 8 AWG | 40 A | 50 A | Termination rated 75 C | Passes defaults |
| Aluminum | 8 AWG | 40 A | 40 A | Termination rated 75 C | Passes defaults |
What 40 A ChangesAt 40 A, both copper and aluminum show 8 AWG under the default short-run assumptions, but they do not have the same usable ampacity. This page is the appliance-band entry point, not a generic permission to reuse every 30 A wiring habit.
Adjacent Amp Ratings
See whether stepping one standard size up or down forces a conductor jump under the same defaults.
| Load | Copper size | Copper OCPD | Aluminum size | Aluminum OCPD |
|---|---|---|---|---|
| 30 A | 10 AWG | 30 A | 8 AWG | 30 A |
| 40 A (this page) | 8 AWG | 40 A | 8 AWG | 40 A |
| 45 A | 8 AWG | 45 A | 6 AWG | 45 A |
A plateau means neighboring amp ratings share a conductor size under these defaults. A jump means a standard breaker change often needs a larger wire; confirm with your real ambient, length and terminations.
40 A Starts the Appliance Band
Appliance / mid branch context for a 40 A circuit.
A 40 A wire-size search commonly comes from a cooktop, range circuit, water heater, 32 A EVSE setting, listed equipment, or a dedicated shop load. The question is usually whether the job has moved beyond the familiar 30 A small-conductor answer.
Under the displayed 75 C termination defaults, 40 A moves copper from 10 AWG at 30 A to 8 AWG. Aluminum is also 8 AWG here, but it has no margin above the displayed 40 A usable ampacity and can move larger on 60 C equipment.
What Changes This Answer
Checks that can change the starting conductor under the displayed defaults.
Separate 30 A from 40 A
The adjacent 30 A page uses 10 AWG copper under these defaults. A 40 A circuit moves copper to 8 AWG.
Watch the 45 A aluminum jump
Copper stays 8 AWG at 45 A under these defaults, but aluminum moves from 8 AWG to 6 AWG.
Read the equipment nameplate
Ranges, cooktops, heaters and listed equipment may specify minimum circuit ampacity and maximum overcurrent protection.
Check continuous-load cases
A 32 A EVSE setting can map to a 40 A circuit after the 125 percent step. A true 40 A continuous load is a different input and should be rerun with continuous load enabled.
Confirm 75 C for 8 AWG aluminum
The aluminum row relies on the displayed 75 C termination default. Equipment limited to 60 C can force a larger aluminum conductor.