What Size Wire for 45 Amps?
- Load
- 45 A
- Distance
- 0 ft entered
- Band
- Appliance / mid branch
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
- Conductor count
- 3 current-carrying
Computed Starting Point
The table uses common defaults. Change the calculator inputs for the actual installation.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 8 AWG | 45 A | 50 A | Termination rated 75 C | Passes defaults |
| Aluminum | 6 AWG | 45 A | 50 A | Termination rated 75 C | Passes defaults |
What 45 A ChangesAt 45 A, the page is not a clean halfway point between 40 A and 50 A. Copper remains 8 AWG under the displayed defaults, but aluminum steps up to 6 AWG, so material choice drives the adjacent-rating difference.
Adjacent Amp Ratings
See whether stepping one standard size up or down forces a conductor jump under the same defaults.
| Load | Copper size | Copper OCPD | Aluminum size | Aluminum OCPD |
|---|---|---|---|---|
| 40 A | 8 AWG | 40 A | 8 AWG | 40 A |
| 45 A (this page) | 8 AWG | 45 A | 6 AWG | 45 A |
| 50 A | 8 AWG | 50 A | 6 AWG | 50 A |
A plateau means neighboring amp ratings share a conductor size under these defaults. A jump means a standard breaker change often needs a larger wire; confirm with your real ambient, length and terminations.
45 A Is the Appliance Middle Step
Appliance / mid branch context for a 45 A circuit.
A 45 A wire-size search usually comes from equipment rather than a general-purpose branch circuit: cooking equipment, heaters, shop equipment, or a manufacturer-specified circuit.
Under the displayed 75 C termination defaults, copper stays at 8 AWG from 40 A to 45 A, while aluminum moves from 8 AWG to 6 AWG. That material split is the useful reason this page deserves its own answer.
What Changes This Answer
Checks that can change the starting conductor under the displayed defaults.
Start from equipment data
A 45 A requirement is usually nameplate-driven. Use listed minimum circuit ampacity, terminal rating and maximum overcurrent protection when they are provided.
Do not reuse 40 A aluminum
Under these defaults, 40 A aluminum is 8 AWG, while 45 A aluminum moves to 6 AWG.
Compare 50 A before rounding up
Do not round a 45 A requirement to 50 A without equipment and load support. Adjacent pages are comparison tools, not permission to change ratings.
Check distance and continuous load
This amp-only answer assumes a non-continuous load, 75 C terminations and no route length. Long runs, continuous loads or 60 C equipment should be rerun with actual inputs.