What Size Wire for 100 Amps at 100 Feet?
- Load
- 100 A
- Distance
- 100 ft
- Band
- 100 A feeder
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
Computed Starting Point
Ampacity and voltage drop under common defaults for this amp and distance.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 3 AWG | 100 A | 100 A | Termination rated 75 C | Passes defaults |
| Aluminum | 1 AWG | 100 A | 100 A | Termination rated 75 C | Passes defaults |
What 100 ft ChangesUnder the default 240 V, noncontinuous 100 A setup, 100 ft does not upsize the conductor from the ampacity-only result. Termination ampacity still governs, but a slightly longer measured route, continuous loading, hotter ambient, or 120 V load can move the job into the voltage-drop pages immediately above it.
Zero-Length vs This Distance
If the distance-adjusted size is larger, voltage drop governed under these defaults.
| Case | Copper size | Copper constraint | Aluminum size | Aluminum constraint |
|---|---|---|---|---|
| Ampacity only (0 ft) | 3 AWG | Termination rated 75 C | 1 AWG | Termination rated 75 C |
| 100 ft (this page) | 3 AWG | Termination rated 75 C | 1 AWG | Termination rated 75 C |
Adjacent Distances at This Amp
Neighboring published lengths for 100 A under the same defaults.
| Distance | Copper size | Aluminum size | Copper constraint |
|---|---|---|---|
| 100 ft (this page) | 3 AWG | 1 AWG | Termination rated 75 C |
| 150 ft | 2 AWG | 1/0 AWG | Voltage drop |
100 ft Is the Short Outbuilding Edge
100 A feeder context for 100 A at 100 ft.
A 100 ft 100 A search is usually a garage, small shop, ADU, or short detached-building feeder where the user wants to know whether the ordinary 100 A conductor still survives once route length is included.
Under the defaults on this page, the zero-length row and the 100 ft row match. That makes this page a boundary check: the route is long enough to ask about drop, but not long enough in this model to change the computed conductor.
What Changes This Long-Run Answer
Checks that matter for distance-governed sizing in this amp band.
Do not round a longer route down
The one-way conductor path includes bends, vertical drops, panel location and trench detours. A route that measures closer to 130-150 ft belongs in the next distance check.
Use 100 ft as a boundary check
Because the zero-length and 100 ft rows match under these defaults, this page tells you drop has not yet beaten ampacity for this exact setup.
Confirm the load is not continuous
A feeder carrying EVSE or another sustained load can need 125 percent sizing before this 100 A answer is even the right input.
Keep the 150 ft jump visible
The adjacent table shows the next published length. If the route grows, copper and aluminum both move to larger conductors under the same assumptions.