What Size Wire for 100 Amps at 150 Feet?
- Load
- 100 A
- Distance
- 150 ft
- Band
- 100 A feeder
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
Computed Starting Point
Ampacity and voltage drop under common defaults for this amp and distance.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 2 AWG | 100 A | 115 A | Voltage drop | Passes defaults |
| Aluminum | 1/0 AWG | 100 A | 120 A | Voltage drop | Passes defaults |
What 150 ft ChangesAt 150 ft, voltage drop becomes the governing constraint for both materials under the page defaults. That means the extra conductor size is buying voltage performance, not extra breaker capacity. If the measured route is actually closer to 100 ft, the previous page may hold; if it is closer to 200 ft, plan for another jump.
Zero-Length vs This Distance
If the distance-adjusted size is larger, voltage drop governed under these defaults.
| Case | Copper size | Copper constraint | Aluminum size | Aluminum constraint |
|---|---|---|---|---|
| Ampacity only (0 ft) | 3 AWG | Termination rated 75 C | 1 AWG | Termination rated 75 C |
| 150 ft (this page) | 2 AWG | Voltage drop | 1/0 AWG | Voltage drop |
Adjacent Distances at This Amp
Neighboring published lengths for 100 A under the same defaults.
| Distance | Copper size | Aluminum size | Copper constraint |
|---|---|---|---|
| 100 ft | 3 AWG | 1 AWG | Termination rated 75 C |
| 150 ft (this page) | 2 AWG | 1/0 AWG | Voltage drop |
| 200 ft | 1 AWG | 2/0 AWG | Voltage drop |
150 ft Is the First Jump Length
100 A feeder context for 100 A at 150 ft.
A 150 ft 100 A run is the classic detached garage or shop feeder where the straight-line distance looked safe, but the measured conductor path is long enough for voltage drop to take over.
This page is not just the 100 ft answer with a different number. Under the same defaults, both copper and aluminum move one size above the zero-length result, and the next 200 ft page moves again.
What Changes This Long-Run Answer
Checks that matter for distance-governed sizing in this amp band.
Measure the installed route
A trench that looks like 120 ft on the plan can become 150 ft after panel location, sweeps, risers and equipment offsets are included.
Do not reuse the 100 ft conductor
Under these defaults, 100 ft is termination-governed while 150 ft is voltage-drop-governed. The smaller 100 ft answer is not the same page.
Check 200 ft before buying
If the final route may grow, price the next distance before ordering. The adjacent table shows another conductor jump at 200 ft.
Separate drop from ampacity
A 2 AWG copper or 1/0 aluminum result here does not authorize a larger breaker. It is still a 100 A feeder answer under the stated defaults.