What Size Wire for 100 Amps at 250 Feet?
- Load
- 100 A
- Distance
- 250 ft
- Band
- 100 A feeder
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
Computed Starting Point
Ampacity and voltage drop under common defaults for this amp and distance.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 1/0 AWG | 100 A | 150 A | Voltage drop | Passes defaults |
| Aluminum | 3/0 AWG | 100 A | 155 A | Voltage drop | Passes defaults |
What 250 ft ChangesAt 250 ft, voltage drop already controls the 100 A answer, and a 50 ft measurement error can move the job into the 300 ft result. The useful decision is not whether to consider drop; it is whether the route is final enough to buy 1/0 copper or 3/0 aluminum instead of pricing the next step now.
Zero-Length vs This Distance
If the distance-adjusted size is larger, voltage drop governed under these defaults.
| Case | Copper size | Copper constraint | Aluminum size | Aluminum constraint |
|---|---|---|---|---|
| Ampacity only (0 ft) | 3 AWG | Termination rated 75 C | 1 AWG | Termination rated 75 C |
| 250 ft (this page) | 1/0 AWG | Voltage drop | 3/0 AWG | Voltage drop |
Adjacent Distances at This Amp
Neighboring published lengths for 100 A under the same defaults.
| Distance | Copper size | Aluminum size | Copper constraint |
|---|---|---|---|
| 200 ft | 1 AWG | 2/0 AWG | Voltage drop |
| 250 ft (this page) | 1/0 AWG | 3/0 AWG | Voltage drop |
| 300 ft | 2/0 AWG | 4/0 AWG | Voltage drop |
250 ft Is the Next Long-Run Cliff
100 A feeder context for 100 A at 250 ft.
A 250 ft 100 A feeder usually means the panel location, trench route, risers and load placement are no longer small details. A route that looked like 220-230 ft on the plan can become the 250 ft page once sweeps, verticals and equipment offsets are counted.
Compared with the refined 200 ft result, both materials move up another size under the same defaults. This page is where the decision shifts from asking whether drop matters to asking how much extra conductor, raceway and lug space the route will consume.
What Changes This Long-Run Answer
Checks that matter for distance-governed sizing in this amp band.
Do not reuse the 200 ft result
Under these defaults, 200 ft lands on 1 AWG copper or 2/0 aluminum. At 250 ft the page result moves to 1/0 copper or 3/0 aluminum.
Measure before buying
Include sweeps, risers, panel offsets and the final equipment location. The difference between an estimated 230 ft and a measured 250 ft can be a conductor order.
Check raceway and lugs early
1/0 copper and 3/0 aluminum change conduit fill, bend space and lug acceptance compared with the shorter-run answer.
Preview 300 ft if the route is unsettled
The next published distance jumps again under the same defaults. Price 300 ft before buying if trench routing or panel location is still moving.