What Size Wire for 100 Amps at 300 Feet?
- Load
- 100 A
- Distance
- 300 ft
- Band
- 100 A feeder
- Defaults
- Non-continuous, 75 C lugs, 86 F, 240 V single-phase
Computed Starting Point
Ampacity and voltage drop under common defaults for this amp and distance.
| Material | Computed size | OCPD | Usable ampacity | Governing constraint | Default check |
|---|---|---|---|---|---|
| Copper | 2/0 AWG | 100 A | 175 A | Voltage drop | Passes defaults |
| Aluminum | 4/0 AWG | 100 A | 180 A | Voltage drop | Passes defaults |
What 300 ft ChangesAt 300 ft, the default result is 2/0 copper or 4/0 aluminum, governed by voltage drop. The conductor is now much larger than the ampacity-only 100 A answer, so raceway size, bend space, pulling difficulty and the possibility of moving equipment become part of the sizing conversation.
Zero-Length vs This Distance
If the distance-adjusted size is larger, voltage drop governed under these defaults.
| Case | Copper size | Copper constraint | Aluminum size | Aluminum constraint |
|---|---|---|---|---|
| Ampacity only (0 ft) | 3 AWG | Termination rated 75 C | 1 AWG | Termination rated 75 C |
| 300 ft (this page) | 2/0 AWG | Voltage drop | 4/0 AWG | Voltage drop |
Adjacent Distances at This Amp
Neighboring published lengths for 100 A under the same defaults.
| Distance | Copper size | Aluminum size | Copper constraint |
|---|---|---|---|
| 250 ft | 1/0 AWG | 3/0 AWG | Voltage drop |
| 300 ft (this page) | 2/0 AWG | 4/0 AWG | Voltage drop |
| 400 ft | 3/0 AWG | 250 kcmil | Voltage drop |
300 ft Is a Long Route Decision
100 A feeder context for 100 A at 300 ft.
A 300 ft 100 A run is no longer a short outbuilding feeder with a little extra length. It is a long trench, driveway, detached shop, pump house or equipment-pad route where conductor size, raceway fill and equipment placement all compete with each other.
Under the defaults on this page, both materials have moved again from the 250 ft result. This is the distance where the page should help a user decide whether to keep carrying the full 100 A load or revisit where the feeder terminates.
What Changes This Long-Run Answer
Checks that matter for distance-governed sizing in this amp band.
Treat 300 ft as a layout checkpoint
Before ordering 2/0 copper or 4/0 aluminum, confirm whether the panel, transformer, load center or equipment pad can move closer to reduce the full-load run.
Compare 250 ft and 400 ft
The 250 ft page is one step smaller, while 400 ft moves to a different conductor class. Use the adjacent table to see which side your measured route actually falls on.
Verify 4/0 aluminum landing
If aluminum is the cost path, confirm the equipment lugs, torque range, bend space and raceway fill accept 4/0 aluminum before treating the result as buyable.
Use actual load current when lower
If the feeder rarely carries the full 100 A, run the calculator with the design current that will actually flow. Voltage drop follows current, not the panel label.